PROGRAMMABLE PARAMETERS: 

 
There are 15 programmable parameters with their Factory Default Settings listed in this section. The table 
below indicates what these parameters are, along with the permitted values and the original settings. 

Program No. 

Description 

Default 

Range 

P-1 Operating 

Mode 

0 = Auto 
1 = Cool Only 
2 = Heat Only 

P-2 

High Fan Speed Limit (arbitrary units) 

95 

65 - 95 

P-3 

Low Fan Speed Limit  (arbitrary units) 

64 

30 - 64 

P-4 

Compressor Staging Time Delay 

135 

5 - 135 seconds 

P-5 

Temperature Sensor Calibration 

Ambient Temp 

Ambient ± 10° F 

P-6 FAILSAFE 

 

0 = Minimum Protection 
1 = Continuous - No Display 
2 = Continuous with Display 
3 = Four Failures, Reset Required 

P-7 

Reserved For Future Option 

 

 

P-8 

De-Icing Cycle  

OFF 

OFF 
1 to 3 Minutes 

P-9 

Reserved For Future Option 

 

 

P-10 

Display Brightness Control 

4 = Low 
13 = Maximum  

P-11 

Display ° Fahrenheit or ° Celsius 

°F 

°F = Fahrenheit Displayed 
°C = Celsius Displayed 

P-12 

Cycle Pump With Compressor or 
Continuous Pump 

OFF 

OFF = Cycle with Compressor 
On  = Continuous Pump 

P-13 

Reverse Fan Speeds During Heating Mode 

rEF 

nor = Normal Fan Operation 
rEF = Reversed Fan In Heating 

P-14 

Continuous Fan or Cycle 
Fan with Compressor 

con 

con = Continuous Fan Operation 
CYC = Cycle Fan With Comp. 

P-15 

Reverse Cycle Heating or Electric Heat  

nor 

nor = Reverse Cycle Heating 
ELE = Electric Heater Installed 

P-16 

Fan motor type selection: 
Shaded pole or split capacitor. 

SC for HSA16K 

SP for HSA9K 

SP = Shaded Pole Fan Motor 
SC = Split Cap. Fan Motor 

P-17 

Reset Memorized Programming Defaults 

Nor 

rSt = Reset Defaults 
nor = Normal 

 

P-1: Operating Mode 

Most Radome systems do not support heat mode operation, so this parameter should be set to "1", for 
Cool Only mode.  If your particular system has the electric heater option installed, this parameter can 
then be set to "0" for Automatic mode, "1" for Cool Only mode, or "2" for Heat Only mode. 

 

P-2: High Fan Limit - N/A 
P-3: Low Fan Limit - N/A 
P-4: Compressor Staging Time Delay - N/A 

 

P-5: Temperature Calibration 

Use this feature to calibrate the ambient sensor. Select P-5 and the ambient temperature appears in the 
display. Use the up and down keys to set the correct reading. The temperature in the display will 
increase or decrease as required. 

Содержание RADOME A/C

Страница 1: ...RADOME A C with Passport I O Installation Operation Maintenance Manual L 2283 Revised 9 29 04...

Страница 2: ...e display panel Face plate air sensor for accurate temperature control LED temperature displayed in Fahrenheit or Celsius Compressor pressure protection This manual is intended to provide the informat...

Страница 3: ...ing servicing repairing or disposing of an appliance or industrial process refrigeration to knowingly vent or otherwise knowingly release or dispose of any Class I or Class II substance used as a refr...

Страница 4: ...CZ 230VAC 50 60HZ 1Ph 11 E1010009 HSA16K C CZ CZ50 115 230VAC 50 60HZ 1Ph 12 E1010010 HSAS16K CZ CZ50 Split 230VAC 50 60HZ 1Ph 13 E1010013 HSAS16K Z Z50 Split W ELECTRIC HEAT 230VAC 50 60HZ 1Ph 14 E1...

Страница 5: ...MENTS FOR IGNITION PROTECTION DO NOT INSTALL IN SPACES CONTAINING GASOLINE ENGINES TANKS LPG CPG CYLINDERS REGULATORS VALVES OR FUEL LINE FITTINGS FAILURE TO COMPLY MAY RESULT IN INJURY OR DEATH NOTIC...

Страница 6: ...l connections shall be made with solderless terminals Turn off a c power supply circuit breaker before opening electric box Each a c unit installed requires its own dedicated circuit breaker OPERATION...

Страница 7: ...le cooling FAN LED NOT USED ON RADOME A C HEAT LED NOT USED ON RADOME A C DISPLAY WINDOW Shows current temperature Also used in viewing and setting program parameters AIR SENSOR Dome temperature is de...

Страница 8: ...h the system off press and hold the POWER button for five seconds until the letter P appears in the display window Release the button and the first parameter s setting appears followed by P 1 TO SELEC...

Страница 9: ...nuous Pump P 13 Reverse Fan Speeds During Heating Mode rEF nor Normal Fan Operation rEF Reversed Fan In Heating P 14 Continuous Fan or Cycle Fan with Compressor con con Continuous Fan Operation CYC Cy...

Страница 10: ...ut down delay P 7 Reserved for Future Option P 8 De Icing Cycle N A P 9 Reserved for Future Option P 10 Display Brightness Control The display brightness can be adjusted from four 4 to thirteen 13 Fou...

Страница 11: ...condenser air flow Check for obstructions at condenser air inlet Fan is not running See below Coil is iced See below HPF is displayed on panel See below LPF is displayed on panel See below No air flow...

Страница 12: ...date of manufacture Labor is not covered Environmental Air Systems Inc will repair or replace at its option components found to be defective due to faulty materials or workmanship when such component...

Страница 13: ...275 Contact Gene Lawing Tel 206 660 2240 Fax 425 740 0246 E mail glawing earthlink net Delaware Maryland Pennsylvania Virginia New York New Jersey Connecticut Maine Massachusetts New Hamphsire Rhode I...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...drews Ave Ext Pompano Beach FL 33069 1497 USA Phone 954 973 2477 Facsimile 954 979 4414 Fleets Industrial Estate 26 Willis Way Poole Dorset BH15 3SU England Phone 44 0 870 3306101 Facsimile 44 0 870 3...

Отзывы: