P-6: Fail Safe Level 

When a fault is detected Passport I/O will display one of the following Mnemonic fault codes: 

“HPF”… 

Indicates high Freon pressure. 

“LPF”… 

Indicates low Freon pressure. 

“ASF

”… Indicates failed air sensor. 

There are four fail safe levels: 

Failsafe Level 0: 

Only “ASF” detected and displayed. The control will

 

shut down and will not restart 

until the fault is repaired.

 

Once the fault is repaired the control will restart. 

Failsafe Level 1: 

All actions in level 0 plus all other faults detected but

 

not indicated. The system shuts 

down for two minutes or

 

until the fault is cleared, whichever is longer. The system

 

will restart if the 

fault is cleared. 

Failsafe Level 2: 

All actions same as level 0 and 1. Faults are indicated.

 

The system shuts down for 

two minutes or until the fault

 

is cleared, whichever is longer. 

Failsafe Level 3: 

All actions the same as level 0, 1 and 2. The system

 

shuts down for two minutes or 

until the fault is cleared,

 

whichever is longer. The system will lockout after four

 

consecutive “HPF” 

or “LPF” faults. Pressing the Power

 

Button once to Off Mode, and pressing again to On

 

Mode, 

clears the lockout. 

NOTE: • “HPF” 

is not indicated and does not cause

 

lockout in Heat Mode. 

• “LPF” 

has a ten minute shut down delay. 

 

P-7: Reserved for Future Option 
P-8: De-Icing Cycle - N/A 
P-9: Reserved for Future Option 

 

P-10: Display Brightness Control 

The display brightness can be adjusted from four (4) to thirteen (13). Four being is the dimmest and 
thirteen the brightest. 

 

P-11: Fahrenheit or Celsius Selection 

The default setting is °F; select °C for Celsius readings displayed in tenths, i.e. 22.2°. 

 

P-12: Cycle Pump with Compressor - N/A 
P-13: Reverse Automatic Fan Speeds During Heating - N/A 
P-14: Cycle Fan with Compressor - N/A 

 

P-15: Reverse Cycle or Electric Heat 

Most Radome systems do not support heat mode operation, so this parameter setting should remain at 
the factory setting of “nor”.  If your particular system has the electric heater option installed, then this 
parameter should be set to "ELE" for Electric Heater Installed. 
 

P-16: Fan Motor Selection 

Model HSA(S)16K has a split capacitor fan motor (SC); HSA9K has a shaded pole fan motor (SP). 
 

P-17: Reset Memorized Defaults 

The default programming parameters can be reset by entering the program mode and selecting “rSt”. 
This restores the programmable parameters to the default values. The default parameters listed in the 
table may be altered by the installing dealer or end user. Once 

new 

defaults are entered (see dual button 

functions) and memorized the factory defaults will be over written. The original factory program 
parameters as listed in the table will have to be restored manually. 

Содержание RADOME A/C

Страница 1: ...RADOME A C with Passport I O Installation Operation Maintenance Manual L 2283 Revised 9 29 04...

Страница 2: ...e display panel Face plate air sensor for accurate temperature control LED temperature displayed in Fahrenheit or Celsius Compressor pressure protection This manual is intended to provide the informat...

Страница 3: ...ing servicing repairing or disposing of an appliance or industrial process refrigeration to knowingly vent or otherwise knowingly release or dispose of any Class I or Class II substance used as a refr...

Страница 4: ...CZ 230VAC 50 60HZ 1Ph 11 E1010009 HSA16K C CZ CZ50 115 230VAC 50 60HZ 1Ph 12 E1010010 HSAS16K CZ CZ50 Split 230VAC 50 60HZ 1Ph 13 E1010013 HSAS16K Z Z50 Split W ELECTRIC HEAT 230VAC 50 60HZ 1Ph 14 E1...

Страница 5: ...MENTS FOR IGNITION PROTECTION DO NOT INSTALL IN SPACES CONTAINING GASOLINE ENGINES TANKS LPG CPG CYLINDERS REGULATORS VALVES OR FUEL LINE FITTINGS FAILURE TO COMPLY MAY RESULT IN INJURY OR DEATH NOTIC...

Страница 6: ...l connections shall be made with solderless terminals Turn off a c power supply circuit breaker before opening electric box Each a c unit installed requires its own dedicated circuit breaker OPERATION...

Страница 7: ...le cooling FAN LED NOT USED ON RADOME A C HEAT LED NOT USED ON RADOME A C DISPLAY WINDOW Shows current temperature Also used in viewing and setting program parameters AIR SENSOR Dome temperature is de...

Страница 8: ...h the system off press and hold the POWER button for five seconds until the letter P appears in the display window Release the button and the first parameter s setting appears followed by P 1 TO SELEC...

Страница 9: ...nuous Pump P 13 Reverse Fan Speeds During Heating Mode rEF nor Normal Fan Operation rEF Reversed Fan In Heating P 14 Continuous Fan or Cycle Fan with Compressor con con Continuous Fan Operation CYC Cy...

Страница 10: ...ut down delay P 7 Reserved for Future Option P 8 De Icing Cycle N A P 9 Reserved for Future Option P 10 Display Brightness Control The display brightness can be adjusted from four 4 to thirteen 13 Fou...

Страница 11: ...condenser air flow Check for obstructions at condenser air inlet Fan is not running See below Coil is iced See below HPF is displayed on panel See below LPF is displayed on panel See below No air flow...

Страница 12: ...date of manufacture Labor is not covered Environmental Air Systems Inc will repair or replace at its option components found to be defective due to faulty materials or workmanship when such component...

Страница 13: ...275 Contact Gene Lawing Tel 206 660 2240 Fax 425 740 0246 E mail glawing earthlink net Delaware Maryland Pennsylvania Virginia New York New Jersey Connecticut Maine Massachusetts New Hamphsire Rhode I...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...drews Ave Ext Pompano Beach FL 33069 1497 USA Phone 954 973 2477 Facsimile 954 979 4414 Fleets Industrial Estate 26 Willis Way Poole Dorset BH15 3SU England Phone 44 0 870 3306101 Facsimile 44 0 870 3...

Отзывы: