6
P-6: Fail Safe Level
When a fault is detected Passport I/O will display one of the following Mnemonic fault codes:
“HPF”…
Indicates high Freon pressure.
“LPF”…
Indicates low Freon pressure.
“ASF
”… Indicates failed air sensor.
There are four fail safe levels:
Failsafe Level 0:
Only “ASF” detected and displayed. The control will
shut down and will not restart
until the fault is repaired.
Once the fault is repaired the control will restart.
Failsafe Level 1:
All actions in level 0 plus all other faults detected but
not indicated. The system shuts
down for two minutes or
until the fault is cleared, whichever is longer. The system
will restart if the
fault is cleared.
Failsafe Level 2:
All actions same as level 0 and 1. Faults are indicated.
The system shuts down for
two minutes or until the fault
is cleared, whichever is longer.
Failsafe Level 3:
All actions the same as level 0, 1 and 2. The system
shuts down for two minutes or
until the fault is cleared,
whichever is longer. The system will lockout after four
consecutive “HPF”
or “LPF” faults. Pressing the Power
Button once to Off Mode, and pressing again to On
Mode,
clears the lockout.
NOTE: • “HPF”
is not indicated and does not cause
lockout in Heat Mode.
• “LPF”
has a ten minute shut down delay.
P-7: Reserved for Future Option
P-8: De-Icing Cycle - N/A
P-9: Reserved for Future Option
P-10: Display Brightness Control
The display brightness can be adjusted from four (4) to thirteen (13). Four being is the dimmest and
thirteen the brightest.
P-11: Fahrenheit or Celsius Selection
The default setting is °F; select °C for Celsius readings displayed in tenths, i.e. 22.2°.
P-12: Cycle Pump with Compressor - N/A
P-13: Reverse Automatic Fan Speeds During Heating - N/A
P-14: Cycle Fan with Compressor - N/A
P-15: Reverse Cycle or Electric Heat
Most Radome systems do not support heat mode operation, so this parameter setting should remain at
the factory setting of “nor”. If your particular system has the electric heater option installed, then this
parameter should be set to "ELE" for Electric Heater Installed.
P-16: Fan Motor Selection
Model HSA(S)16K has a split capacitor fan motor (SC); HSA9K has a shaded pole fan motor (SP).
P-17: Reset Memorized Defaults
The default programming parameters can be reset by entering the program mode and selecting “rSt”.
This restores the programmable parameters to the default values. The default parameters listed in the
table may be altered by the installing dealer or end user. Once
new
defaults are entered (see dual button
functions) and memorized the factory defaults will be over written. The original factory program
parameters as listed in the table will have to be restored manually.
Содержание RADOME A/C
Страница 1: ...RADOME A C with Passport I O Installation Operation Maintenance Manual L 2283 Revised 9 29 04...
Страница 14: ......
Страница 15: ......
Страница 16: ......
Страница 17: ......
Страница 18: ......
Страница 19: ......
Страница 20: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......