ELECTRA-flo G5 Transmitter Thermal Airflow & Temperature Measurement System 1015-3 - 07/18
15
STANDARD OBJECT TYPES SUPPORTED
Device Object
Property
Default Value
Read-Only
or Writable
Comment
Object Identifier
1
Writable
0 – 4,194,303
Object Name
ELECTRA-flo
Writable
Alpha-numeric; 16 char limit.
Linked to “Custom ID” setting in the
Service Menu.
Also displays on the bottom of the
LCD display on transmitter.
Object Type
Device
Read-only
System Status
Operational
Read-only
Vendor Name
Air Monitor Corporation
Read-only
Model Name
ELECTRA-flo
Read-only
Location
Default Location
Writable
Description
Thermal
Writable
Protocol Version
1
Read-only
Protocol Revision
9
Read-only
Services Supported
readProperty, readPropertyMultiple,
writeProperty,
deviceCommunicationControl,
reinitializedevice, who-has, who-is
Read-only
Object Types Supported Analog-input, Device
Read-only
Object List
Varies: (device, 1), (analog input, 0 -
X) where X = 1 + (No. of sensors *2)
Read-only
Max ADPU Length
128
Read-only
Segmentation Supported No Segmentation
Read-only
APDU Time-out
3000
Read-only
# of APDU Retries
3
Read-only
Max Master
127
Writable
Device Address Binding
{}
Read-only
Database Revision
3
Read-only
Analog Inputs
Property
Default Value
Read-only or Writable
Object Identifier
Analog Input-0 to Analog Input-X
Read-only
Object Name
Various
Read-only
Object Type
Analog-input
Read-only
Present Value
REAL
Read-only
Status Flags
F, F, F, F
Read-only
Event State
Normal
Read-only
Out of Service
FALSE
Read-only
Description
Various
Writable
Location
Various
Writable
Units
Various
Read-only