ELECTRA-flo G5 Transmitter Thermal Airflow & Temperature Measurement System 1015-3 - 07/18
12
Display Configuration
ENT - Accept ESC - Del/Leave UP/DN - Change
Line 1:
Flow
Velocity
Temperature
ID
100%
60 min
Line 2:
Line 3:
Line 4:
Brightness:
Inactivity Timeout:
Display Configuration
This screen allows the user to set parameters on various lines
of the display. There are four display lines on the
ELECTRA-flo G5.
Line 1
- Flow (typical), Velocity or
Temperature.
Line 2 -
Velocity, Flow or None.
Line 3 -
Temperature, Flow or None.
Line 4 -
Custom ID or None. This
field is settable over BACnet or through the Service Menu. It
is typically used to describe the transmitter location in the
building.
Brightness
- Allows the user to set the brightness of
the display in real time.
Inactivity Timeout
- The time period
which holds the display in menu mode. When the timer
expires, the display is returned to the main display screen
showing the process values.
Note: The optional true dual channel version of the
ELECTRA-FLO G5 only displays flow.
Analog Output Configuration
The ELECTRA-flo G-5 transmitter is equipped with dual
analog outputs. The Analog Output Configuration menu
configures the analog output type, parameter and filter.
Output Type:
4-20 mADC, 0-5 VDC or 0-10 VDC
Output 1 and 2:
Flow, Velocity or Temperature
Optional True Dual Channel Version
Output 1:
Flow, Temperature or SYS1 Flow Add
Output 2:
Flow, Temperature or SYS2 Flow Subt
The Filter has a minimum setting of 0 to a maximum setting
of 10. To disable the Filter, select Off.
Display Average Filter
The Display Averaging Filter filters the data shown on the
display. It affects all elements of the display. The
Filter
has
1-10 settings. One is the lightest filter, and 10 represents the
heaviest filter. It also has an ‘Off’ setting.
Analog Output Configuration
ENT - Accept ESC - Leave UP/DN - Change
Output Type:
4-20 mA
Flow
Temperature
4
Output 1:
Output 2:
Filter:
i
IMPORTANT NOTE
Optional true dual channel version
Sys1 and Sys2 full scale flow values are set in the Sys1 and Sys2 flow configuration menus
Sys1 Flow Add full scale = Sys1 max flow + Sys2 max flow
Sys2 Flow Subt full scale = Sys1 flow max
Display Averaging Filter
ENT - Accept ESC - Del/Leave UP/DN - Change
Filter:
4