ELECTRA-flo
Air Monitor Corporation
116-053-00.P65 (7/06)
ELECTRA-flo
- IO&M Manual
6.5 – SENSOR FAULT CODE DEFINITIONS
1. While in Main Menu, use or to scroll to:
Sensor Fault Code
Definitions
2. Press . Display will indicate:
Sensor Fault Code
Fault Code: 01
Sensor has not
responded.
3.
Use or to scroll through all Codes for their definitions. The following chart shows all Sensor Fault
Codes and their definitions.
4. When done, press and display will return to previous menu (see Step 1).
UP
UP
DN
ENT
®
ESC
DN
SECTION 6 – CALIBRATION
- Sensor Fault Display Selection
→
Sensor Fault Code Definition
- Averages Fault Code Definition
Sensor Fault Code
Fault Code: 01
Sensor has not
responded.
Operator Menu
Sensor Fault Code
See Sensor Fault
Code List for all
codes.
Sensor Fault Code
01
02
04
08
16
24
32
40
48
56
Definition
Sensor has not responded
Sensor response address incorrect
Sensor response command incorrect
Velocity has over-ranged
Volume has over-ranged
Velocity and Volume have over-ranged
Temperature has over-ranged
Velocity and Temperature have over-ranged
Velocity and Volume have over-ranged
Velocity, Volume, and Temperature have over-ranged
31