The Supervisor menu allows individual sensors to be enabled or disabled, scan all sensors for status, and perform
diagnostics on any fault conditions.
1. To enter the Supervisor Menu, press and at the same time. The display will indicate:
ENTER PASSWORD FOR
SUPERVISOR MENU
XXXXX
Note: If Supervisor Menu password has been bypassed, display will indicate as shown in Step 3 below.
2. Using and scroll to the numeric password for the Supervisor Menu. From the Factory, password is
set to 2,222.
3. Once password is displayed, press , and the display will indicate:
SUPERVISOR MENU
4. Press , and the display will indicate:
SUPERVISOR PASSWORD
SELECTION
By using and , supervisor can scroll through the following selections.
Once the desired selection is displayed, press to enter its sub-menu.
6 – SUPERVISOR MENU
ESC
®
ENT
DN
UP
DN
ENT
UP
DN
MENU SELECTION
DESCRIPTION
ENT
SECTION 6 – CALIBRATION
Supervisor Password Selection
Sensor Management
Diagnostic Display Selection
Sensor Fault Display Selection
Sensor Fault Code Definitions
Averages Fault Code Definitions
Power Cycle Sensor Network
Supervisor Menu Exit
Allows for the selection of password for the Supervisor menu, and the
option to bypass the password.
Allows for the scanning of the sensor network for active and/or enabled
sensors. Also allows for the enabling/disabling of individual sensors.
Displays each sensor's current reading of velocity and temperature.
Displays any sensor that currently has a fault condition and the fault
code.
Displays definitions of all sensor fault codes.
Displays definitions of all averages fault codes.
Allows for the cycling of power to the sensors.
Returns display to
Normal