ELECTRA-flo
- IO&M Manual
5.13 – K-FACTOR CONFIGURATION
Caution
In the majority of applications, the use of a K-Factor is neither required nor desirable.
Before using the K-Factor feature, contact the Service Department (see Section 10) to review
the application and obtain assistance in determining the K-Factor gain and bias values.
Turns K-factor function ON or OFF, calculate a K-Factor gain and bias from measured data, or select a K-Factor gain
value and K-Factor bias value.
Note: If K-Factor is ON, Process displays will have an asterisk (*) after the description (i.e
.
FLOW*
).
SECTION 5 – OPERATION
22
- Transmitter Outut Calibration
→
K - Factor Configuration
- OPERATOR MENU EXIT
Default selection shown.
Available selections:
- K - Factor Off/On Selection
- Calculate K-Factor? Selection
- Numbr of Data Points Selection
1
- Measured Point 1 Selection
1
- Measured Point 2 Selection
1,2
- Measured Point 3 Selection
1,2
- Reference Point 1 Selection
1
- Reference Point 2 Selection
1,2
- Reference Point 3 Selection
1,2
- K-Factor Gain Value
1
- K-Factor Bias Value
1
- K - Factor Gain Selection
3
- K - Factor Bias Selection
3
- Return to MAIN MENU
K- Factor Gain
1.000
0.400 to 5.000 *
0.001 increments
K- Factor Configuration
Return to
MAIN MENU
-25.00 to 25.00%
in 0.01 increments
K- Factor Bias
0.00 %
K- Factor Off / On
OFF
OFF or ON
1
Available only if YES is selected in Calculate
K-Factor?
2
Depends on Number of Data Points selected.
CalculateK-Factor?
NO
NO or YES
Numbr of Data Points
One Pair
One Pair
Two Pairs
Three Pairs
Measured Point 1
1,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Measured Point 2
5,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Measured Point 3
9,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 1
1,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 2
5,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 3
9,000 CFM
U
ses Process Units
& Format Selected
in Process Config.
3
Available only if NO is selected in Calculate
K-Factor?
K-Factor Gain
XXXX
K-Factor Bias
XXX %
Operator Menu
Gain is calculated
from data entered
above.
Gain is calculated
from data entered
above.
*Available range depends
on operating span versus
natural span.