ELECTRA-flo
Air Monitor Corporation
116-053-00.P65 (7/06)
ELECTRA-flo
- IO&M Manual
SECTION 5 – OPERATION
5.8 – FLOW CONFIGURATION
This Operator Menu selection is where all application specific data is entered to configure the ELECTRA-flo for a unique
application. Typical data includes: Units of Measure, Duct Type and Size, Flow Type, Units and Conditions, and Output
Lockdown.
Note:
The Factory has entered data in this section based on customer supplied information. Data can be reviewed
and verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information sheet
provided separately. Review this information
BEFORE
making any changes, as they can have a significant
effect on the operation of the ELECTRA-flo.
13
- OPERATOR MENU Exit.
→
Flow Configuration
- Display Configuration
Default selection shown.
Available selections:
- Dimensional Units Selection
- Temperature Units Selection
- Duct Shape Selection
- Duct Height Selection
1
- Duct Width Selection
1
- Duct Diameter Selection
2
- Duct Area Selection
3
- Actual or Standard Selection
- Site Elevation Selection
- Volume Units Selection
- Design Full Range Selection
- Input Lockdown Selection
- Return to MAIN MENU
Flow Configuration
Return to
MAIN MENU
Dimensional Units
U.S.
U.S. or METRIC
1
Available only if RECTANGULAR or OVALROUND is
selected as Shape.
2
Available only if ROUND is selected as Shape.
Dimensional Units
°F
°F or °C
Duct Shape
RECTANGULAR
RECTANGULAR,
ROUND, OVAL or
OTHER
Duct Height
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Width
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Area
XX.XX Sq. Ft.
0.00 to 100.00 Sq.Ft.
0.000 to 10.000 Sq.M.
Actual or Standard
ACTUAL
Actual or
Standard
Site Elevation
0 Feet
0 to 15,000 Feet
0 to 4,572 Meters
Volume Units
ACFM
See UNITS list for
available
selections
3
Available only if OTHER is selected as Shape.
Design Full Range
XX,XXX ACFM
Maximum Full Range
XX,XXX ACFM
4
Input Lockdown
4.0% Max Velocity
Operator Menu
Design value
adjustable up to
maximum value.
0.0% to 100.0%
Duct Diameter
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
4
Maximum Full Range is