background image

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

WARNING: 

TO REDUCE THE RISK OF FIRE, DO NOT STORE 

OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN 

THE VICINITY OF THE HEATER.

SECTION 1

Preparing the Exhaust Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the 

exhaust fan you should have:

 

 

1 - Grill

 

 

1 - Damper Assembly (attached)

 

 

4 - Mounting Rails

 

 

1 - Mounting Flange

 

 

1 - Instruction/Safety Sheet   

2. 

Choose the location for your fan. To ensure the best air and sound performance, it is 

recommended that the length of ducting and the number of elbows be kept to a minimum, 

the radius of each elbow be as large as possible for the installation, and that insulated 

hard ducting be used. Larger duct sizes will reduce noise and airflow restrictions. 

This fan will require at least 7¾

 of clearance in the ceiling or wall (including drywall 

thickness), and will mount through drywall up to ¾

 thick.

3. 

No additional vibration deadening materials are needed for this fan.

SECTION 2

New Construction

1. 

Install the rails into the mounting channel on the housing. Center the mounting channel in 

the slots on the housing, then from inside the housing tighten the mounting channel nuts 

so the channel is securely in place. Position the housing next to the joist. Line up housing 

so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or 

nails (not included) to the joists and slide the housing into the final position 

(Figure 1).

SECTION 3

Existing Construction

1. 

Set housing in position between the joist and trace an outline onto the ceiling material 

(Figure 2).

 Set housing aside and cut opening, being careful not to cut or damage any 

electrical or other hidden utilities. Install the rails into the mounting channel on the 

housing. Center the mounting channel in the slots on the housing, then from inside the 

housing tighten the mounting channel nuts so the channel is securely in place. Position 

the housing in the previously cut hole so that it is flush with the finished ceiling. Secure 

the ends of the rails to the joists 

(Figure 1).

www.airkinglimited.com

6727906 Rev. C 11-18

2 of 12

SECTION 4

Ducting

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND 

NATIONAL BUILDING CODES.

NOTE:

 The ducting from this fan to the outside of the building has a strong effect on the air 

flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible 

for best performance, and avoid installing the fan with smaller ducts than recommended. 

Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed 

with existing ducts may not achieve their rated air flow.

1. 

Connect the ducting to the fan’s duct collar 

(Figure 3).

 Secure in place using tape 

or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is 

recommended that low restriction termination fittings be used.

SECTION 5

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

WARNING:

 THIS UNIT MUST BE WIRED ON A SEPARATE 20 

AMP CIRCUIT.

WARNING:

 

USE APPROPRIATELY SIZED COPPER 

CONDUCTORS ONLY RATED FOR AT LEAST 75°C.

CAUTION:

 ALL 

ELECTRICAL CONNECTIONS MUST 

BE MADE IN ACCORDANCE WITH LOCAL CODES, 

ORDINANCES, OR NATIONAL ELECTRICAL CODE. IF 

YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING 

ELECTRICAL WIRING, SECURE THE SERVICES OF A 

QUALIFIED ELECTRICIAN.

1. 

Remove the wire compartment cover inside the unit 

by unscrewing the screw holding it in place. Set 

aside in a safe place 

(Figure 4).

2. 

Remove the required electrical knockouts on the 

wire compartment using a straight-blade screw driver 

(Figure 4).

CAUTION:

 

USE APPROPRIATELY RATED WIRES FOR ALL 

CONNECTIONS

3. 

Run a ground wire from the power source to the wire compartment and connect to the 

green ground wire inside the compartment. Run a White (Neutral) wire from the power 

source to the wire compartment and connect to the three (3) white wires inside the 

compartment. Run five (5) hot wires from the wall switches (not included) to the wire 

compartment. Make all the wire connections as follows:

 

Wall Switch:

 Connect the hot wire that will energize the wall switches to the orange 

wire from the wire connector in the wire compartment. Additional jump wires may be 

need at the wall switches depending on the type and style of switches used.

 

Heater Function:

 Connect one of the hot wires from the wall switch to the yellow wire 

from the wire connector in the wire compartment.

 

Fan Function:

 Connect one of the hot wires from the wall switch to the black wire from 

the wire connector in the wire compartment.

 

Light Function:

 Connect one of the hot wires from the wall switch to the blue wire from 

the wire connector in the wire compartment.

 

Night Light Function:

 Connect one of the hot wires from the wall switch to the red wire 

from the wire connector in the wire compartment 

(Figure 5).

Ducting

Duct 

Collar

Figure 3

Figure 2

Joist

Housing

Joist

Mounting Rails

Figure 1

Figure 4

Screw

Содержание AKF9110

Страница 1: ...LOWING a Installation work and electrical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire related construction b Use copper wire only c S...

Страница 2: ...e and energy use of the fan Use the shortest straightest duct routing possible for best performance and avoid installing the fan with smaller ducts than recommended Insulation around the ducts can red...

Страница 3: ...g it up into the slot furthest from the wire compartment on the fans housing Attach the 6 pin quick connect from the grill to the 6 pin connector on the top of the wire cover The cord will only fit on...

Страница 4: ...u specific legal rights You may also have other rights which vary from state to state and province to province Proof of purchase is required before a warranty claim will be accepted CUSTOMER SERVICE T...

Страница 5: ...lar Assembly 5S1202121 4 1 Blower Assembly 5S2202013 5 1 Wire Compartment Cover 5S1252001 6 1 Heater Assembly 5S1252002 7 2 Grill Springs 5S1202046 8 1 Ceiling Flange 5S1239024 9 1 Grill Assembly 5S12...

Страница 6: ...www airkinglimited com 6727906 Rev C 11 18 6 of 12 NOTES...

Страница 7: ...de d Lors de coupe ou de per age des murs et plafonds ne pas endommager le filage lectrique et autres utilit s cach es AVERTISSEMENT POUR USAGE DE VENTILATION G N RALE EXCLUSIVEMENT NE PAS UTILISER PO...

Страница 8: ...n de ventilateur Connectez un des fils chauds de l interrupteur mural au fil noir du connecteur du c ble dans le compartiment de fil Fonction de lumi re Connectez un des fils chauds de l interrupteur...

Страница 9: ...ion rapide de 6 broches de la grille au connecteur de 6 broches sur le dessus du couvercle du compartiment de c blage Le c ble ne s ins re que d une fa on dans la prise Installez l autre ressort et po...

Страница 10: ...00 Notre quipe de service la client le est disponible pour vous aider avec des questions sur le produit les adresses des centres de service et les pi ces de rechange Vous pouvez la rejoindre du lundi...

Страница 11: ...e de la Soufflante 5S2202013 5 1 Couvercle du Compartiment de C blage 5S1252001 6 1 Assembl e de chauffage 5S1252002 7 2 Ressorts de la grille 5S1202046 8 1 Bride du plafond 5S1239024 9 1 Assembl e d...

Страница 12: ...www airkinglimited com 6727906 Rev C 11 18 12 of 12 REMARQUE...

Отзывы: