42
Defrost cut-
out
temperature
Setting 11
•
Press "Settings" button to advance to
Setting 11.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 35°F to 50°F.
Factory default is 40°F.
Note: This setpoint must be 1°F/°C
higher than setting 10.
Note: If °C is selected and then
switched back to °F the default cut-out
will change to 41°F.
Defrost check
interval
Setting 12
•
Press "Settings" button to advance to
Setting 12.
•
Press the
“Up” or “Down” arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 30 min at 0
(zero), 1 hour at 1, and then in 1 hour
increments up to a maximum of 12
hours at 12.
Room
temperature
offset
Setting 13
•
Press
“Settings” button to advance to
Setting 13.
•
Press the “Up” or “Down” buttons to
adjust to the desired set point.
Maximum setting is +5°F, minimum
setting is -5°F. Factory default is zero
(0).
Room temperature offset changes the
actual display reading (temperature
only) by the value of this setting.
Example: Sensor reading = 55°F
(13°C)
Setting 13 set to +4
Display reading = 59°F (15°C)