40
Degrees F or
Degrees C
Setting 1
•
Press the “Up” arrow to change
temperature from °F to °C.
•
Press the “Down” arrow to change
temperature from °C to °F.
Low
temperature
alarm setpoint
Setting 2
•
Press “Settings” button to advance to
Setting 2.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. Factory
default is 50°F (10°C).
High
temperature
alarm setpoint
Setting 3
•
Press “Settings” button to advance to
Setting 3.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. Factory
default is 65°F (18°C).
Low humidity
alarm set
point
Setting 4
•
Press “Settings” button to advance to
Setting 4.
•
Press t
he “Up” or “Down” arrow buttons
to adjust to the desired setpoint. Factory
default is 5%.
High humidity
alarm setpoint
Setting 5
•
Press “Settings” button to advance to
Setting 5.
•
Press the up or down arrow buttons to
adjust to the desired setpoint. Factory
default is 95%.
Add or
remove
humidifier
Setting 6
•
Press “Settings” button to advance to
Setting 6.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. Factory
default is zero (0).
Zero (0) = No humidifier
One (1) = Integral Wine Guardian
mounted humidifier
Two (2) = Stand-alone remote mounted
humidifier
Settings
– Press and hold the “Settings” button for five (5) seconds to access the
following settings.
TAP AN ARROW KEY ONCE TO WAKE UP THE CONTROLLER
Содержание WINE GUARDIAN DS025
Страница 13: ...13 Overview of the Evaporator Fig 1...
Страница 14: ...14 Overview of the Condenser Fig 2...
Страница 15: ...15 Refrigeration Illustration Fig 3...
Страница 16: ...16 Wiring Diagram for DS025 WGS40 Fig 4...
Страница 17: ...17 Wiring Diagram for DS025 WGS40 cont Fig 5...
Страница 18: ...18 Wiring Diagram for DS025 WGS40 cont Fig 6...
Страница 19: ...19 Wiring Diagram for DS025 WGS40 cont Fig 7...