44
Basic Troubleshooting
A. Room Temp Too Low
Possible Causes
Recommended Action
Detective temperature sensor
Check and replace
Defective controller
Check and recalibrate or replace
Defective re-heat coil or SSR
Check and replace
Too much evaporator air
Check and adjust mixture or evaporator air and
return air
Low room load
Check room load against capacity of unit. May
need to adjust factory setting of HGBV
B. Room Temp Too High
Possible Causes
Recommended Action
Defective temperature sensor
Check and replace
Defective controller
Check and recalibrate or replace
Defective re-heat coil or SSR
Check and replace
Defective evaporator fan
Check and replace defective parts. See wiring
schematic and parts list
Dirty evaporator coils or filters
Clean coil, Clean or replace filter
Compressor not running
Check unit controls and wiring using schematic.
Replace components as required
Defective evaporator fan
Check and replace defective parts. See wiring
schematic and parts list
Excessive room load
Check room load against design capacity
C. High Room Humidity
Possible Causes
Recommended Action
Too much evaporator air
Check flow volume of makeup air fan
Too warm evaporator coil
May need to adjust factory setting of HGBV
Too much humidification
Check unit for proper operation against service
manufacturer’s service manual
D. Low Room Humidity
Possible Causes
Recommended Action
Too little evaporator air
Check flow volume of makeup air fan
Evaporator coil too cold
May need to adjust factory setting of HGBV
Humidifier not functioning
Check unit for proper operation against service
m
anufacturer’s service manual
Содержание HEPAir 24S050
Страница 11: ...11 General Overview Illustration of the HEPAir Unit may not be representative of all applications Fig 1 Fig 2...
Страница 12: ...12 Overview Illustration of water cooled system Fig 3 Fig 4 Water In...
Страница 13: ...13 Wiring Diagram for HEPAir Fig 5...
Страница 14: ...14 Wiring Diagram for HEPAir with Remote Control Fig 6...
Страница 15: ...15 HEPAir Dimensional Data...