Unit is operating and blows evaporator air,
but the supply air is not colder than the return air from the space
Possible Cause
Solution
Compressor not operating High pressure switch open (button up)
Alarm will appear on thermostat
Condenser airflow is blocked Remove blockage
Clean filter and coil (if needed)
High pressure (HP) switch is open Reset HP switch
See reset instructions on page 65
Possible Cause
Solution
Thermostat set too low on cooling
Reset thermostat to higher cooling
temperature
Heating coil (optional) not operating
Check for temperature rise across coil
Thermostat set too low on heating
Reset thermostat to higher heating
temperature
Thermostat not controlling temperature
Thermostat mounted in improper location
Space Temperature is too cold when unit is not running
Possible Cause
Solution
Too much heat loss to adjacent spaces
Increase insulation around the ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours
Space load is too high
Install additional insulation
Replace with larger sized unit
Problems Controlling Space Temperature
NOTE: Problems are occurring even though the unit seems to be fully operational
evaporator fan blows air into the space and compressor and condenser fan runs.
Содержание HEPAir 24S050
Страница 11: ...11 General Overview Illustration of the HEPAir Unit may not be representative of all applications Fig 1 Fig 2...
Страница 12: ...12 Overview Illustration of water cooled system Fig 3 Fig 4 Water In...
Страница 13: ...13 Wiring Diagram for HEPAir Fig 5...
Страница 14: ...14 Wiring Diagram for HEPAir with Remote Control Fig 6...
Страница 15: ...15 HEPAir Dimensional Data...