8
Figure 2 Front of RJ45 Plug
Caution:
Limit UTP wire runs to 1,000 feet (~330 meters) or less.
Feed the network cable into the housing through the rear or side conduit
hole. Route the cable through the housing and plug it into the RJ 45 jack
shown in
Figure 4.
Avoid putting any tight bends into the network cable.
Caution:
Before proceeding to disconnect the power at its source, be sure
that the unit is of the proper voltage type for the line power.
Connect 24VAC to the unit by inserting the field supply wires into the 2-
position terminal block (supplied) and tighten with a flat blade screwdriver.
Connect Video cable to the unit’s BNC connector.
5.2 Connecting Low Voltage Power & Video Signals
(UTP Models: part number ends in –U)
When powering the unit and transmitting video over unshielded twisted pair
(UTP) wiring, ensure the UTP hub/receiver in the control room is compatible
with the UTP transmitter in the camera housing. Refer to the pinout below
to determine compatibility.
Pin
No.
Wire Color
Pair
Utilization
1
White-Orange
2
Video Signal
2
Orange
2
Video Shield
3
White-Green
3
Data +
4
Blue
1
Power - (Neutral)
5
White-Blue
1
Power + (Line)
6
Green
3
Data -
7
White-Brown
4
Power + (Line)
8
Brown
4
Power - (Neutral)