background image

19

MAINTENANCE

A. GENERAL

1. Check pipes adjacent to cold walls or in unheated

spaces. Insulate and tape them if necessary to be
sure they can't freeze up. Keeping the water moving
at all times will reduce the likelihood of freezing.

2. If there is considerable foreign matter in the boiler

water, the boiler should be shut down and allowed to
cool, then drained and thoroughly flushed out. Drain
the boiler at the drain cock. Pipe the drain cock to a
suitable drain or containment device (if antifreeze is
used). Flush the system to remove remaining matter.
If there is evidence that hard scale has formed on the
internal surfaces, the boiler should be cleaned by
chemical means as prescribed by a qualified water
treatment specialist.

3. There must be no signs of continuous wetness at the

chimney. If signs of continuous wetness are
observed, a qualified service agency must be
consulted to modify the vent configuration to prevent
the formation of condensate, which may damage the
vent pipe.

B. DAILY MAINTENANCE (WITH BOILER

OPERATING)

Daily boiler observation can be performed by the owner.
If any potential problems are found, a qualified installer
or service technician/agency must be notified.

1. Remove any combustible materials, gasoline and

other flammable liquids and substances that generate
flammable vapors from the area where the boiler is
contained. Make certain that the boiler area has
ample air for combustion and ventilation and that
there are no obstructions to the free flow of air to
and from the boiler.

2. Observe general boiler conditions (unusual noises,

vibrations, etc.)

3. Observe operating temperature and/or pressure

gauge on the boiler. Boiler pressure should never be
higher than 5 psi below the rating shown on the
safety relief valve. The valve rating can be found on
the top of the safety relief valve. Boiler temperature
should never be higher than 250°F.

4. Check for water leaks in boiler and system piping.

C. WEEKLY MAINTENANCE (WITH BOILER

OPERATING)

1. Flush float-type low-water cut-off (if used) to remove

sediment from the float bowl as stated in the
manufacturer's instructions.

D. MAINTENANCE OF SAFETY RELIEF

VALVE

1. Check function and maintain safety relief valve as

specified by manufacturer, typically every other
month or every month, per the instructions on the
tag on the safety relief valve.

E. MONTHLY MAINTENANCE (WITH BOILER

OPERATING)

1. Check boiler room floor drains for proper

functioning.

2. Test probe type low-water cut-off (if used) by using

the Push-to-Test Button.

3. Test limit by lowering the limit set point until the

burner shuts down. When proper operation is
confirmed, return the set point to original setting.

4. Follow additional instructions in the Burner Manual

for proving the burner component operation.

F.

MAINTENANCE – ANNUAL

TO CLEAN:

1. Remove top jacket panel and flue collector cover

plate, Item 11 (Figure 2.1 or 2.2).

Disconnect all power to the burner
before accessing combustion
chamber.

WARNING

Turn off power to boiler before
adjusting limit control.

CAUTION

Entire heating system, including
boiler, burner and venting system,
must be inspected at least once a
year by a qualified heating
professional. Boiler is to be cleaned
at least once a year.

NOTICE

Do not use this appliance if any part
has been under water. Improper or
dangerous operation may result.
Immediately call a qualified service
technician to inspect the boiler and
to replace any part of the control
system and any control which has
been under water.

WARNING

Содержание 8HE

Страница 1: ...rywall dust will cause contamination of theburner resultinginpossibleseverepersonalinjury deathorsubstantialpropertydamage Theboilercanonlybeoperatedwithadust free air supply Follow the instruction manual procedures to duct air to the boiler air intake If the boiler has been contaminated by operation with contaminated air follow the instruction manual guidelines to clean repair or replace the boil...

Страница 2: ...IS MANUAL 2 A INSTALLATION CLEARANCE 2 B SPECIAL ATTENTION BOXES 2 1 PREINSTALLATION 3 A CLEARANCES 3 B AIR FOR COMBUSTION AND VENTILATION 3 C CHIMNEY VENT AND DRAFT CONTROL 4 D PLANNING THE LAYOUT 4 2 BOILER PLACEMENT AND ASSEMBLY 5 A SETTING THE BOILER 5 B CONNECTING THE FLUE OUTLET 5 C JACKET ASSEMBLY KNOCKDOWN BOILERS 5 3 PIPING AND CONTROLS 7 A PRESSURE TEST BLOCK ASSEMBLY 7 B BOILER RETURN C...

Страница 3: ...rea of the openings to which they are connected PREINSTALLATION 1 PREINSTALLATION Read carefully study these instructions before beginning work It will save time Study the included drawings Save these instructions for reference This boiler must be installed by a qualified contractor The boiler warranty can be voided if the boiler is not installed maintained and serviced correctly Table 1 1 Clearan...

Страница 4: ...p the chimney However these design features result in higher pressure or draft loss in the boiler This draft loss must be taken into account when installing an oil boiler into a new or old chimney New chimneys are less likely to have poor draft However they must have sufficient draft to support combustion A 06 draft is desirable and preferred Older chimneys may require a replacement liner to have ...

Страница 5: ...ng four 4 5 16 x 1 1 2 studs nuts and washers provided 3 Mount the flue collar adapter and rope seal items 14 and 12 to either the rear boiler section for a rear flue application or to the flue collector cover plate item 11 for a top flue application Use 5 16 hex head bolts for rear flue outlet and sheet metal screws for top flue outlet 4 Attach the rear outlet cover plate item 13 to the remaining...

Страница 6: ...6 BOILER PLACEMENT AND ASSEMBLY Figure 2 1 Steam boiler Figure 2 2 Water boiler See Table 8 1 for parts identification ...

Страница 7: ...rovide piping and controls to protect the boiler from condensation Condensation will damage the boiler and will lead to shortened boiler life and maintenance problems 5 If using a Partner indirect fired water heater or other see Figure 3 6 for typical piping Also refer to additional instructions supplied with the Partner 6 If the boiler is to be used in conjunction with a refrigeration system the ...

Страница 8: ... opposite the standard PA404A using a cross instead of a tee along with a second brass siphon not provided On float boilers install the additional pressure control in the 1 4 tapping on the top of the float low water cut off using a vertical 360º brass siphon not provided c For application of a probe low water cut off use only Hydrolevel CG450 See Figure 7 2 Section 7 for location See also control...

Страница 9: ...9 Figure 3 6 Piping with Indirect Water Tank Figure 3 7 Float Low Water Cut off PIPING AND CONTROLS Figure 3 5 Piping to Isolate Boiler from Chilled Medium on Chiller Systems ...

Страница 10: ...s Hydrolevel 3250 Limit Control Figure 4 6 Steam Boilers with Float LWCO Figure 4 7 Steam Boilers with Probe LWCO 4 ELECTRICAL ELECTRICAL Improper installation of burner harness can allow burner to energize with burner mounting plate open creating a severe burn hazard to boiler maintenance personnel WARNING Figure 4 1 Connecting Ground Wire on Beckett Limit Control In accordance with Section 325 f...

Страница 11: ...11 Figure 4 3 Junction Box Wiring Steam Boilers ELECTRICAL ...

Страница 12: ...12 ELECTRICAL Figure 4 4 Water Boilers Beckett 7600A Limit Control Figure 4 4a Beckett AquaSmart 7600A Limit Control Wiring Details ...

Страница 13: ...13 Figure 4 5 Water Boilers Hydrolevel 3250 Limit Control ELECTRICAL Figure 4 5a Hydrolevel HydroStat 3250 Limit Control Wiring Details ...

Страница 14: ...14 ELECTRICAL Figure 4 7 Steam with Probe Low Water Cut off Figure 4 6 Steam with Float Low Water Cut off ...

Страница 15: ...ing down the thermostat and moving the main boiler service switch to the off position 4 See burner manufacturer s manual for further information regarding the burner C CHECK BOILER CONTROLS 1 Limit and Operating Controls a Lower the set point of each control until the burner shuts down Note that the system pressure or temperature corresponds to the desired set point b Return the controls to the de...

Страница 16: ... flow out of the valve 7 Turn on burner Allow boiler water to heat up to just below steaming 180 200 F Do not allow boiler to steam steaming mixes up contaminants instead of floating them at surface 8 Open make up water valve to continually feed water to boiler Adjust flow to maintain water temperature at 180 200 F 9 Continue skimming boiler until water flowing from skim tapping flows clear This w...

Страница 17: ... DEL 150 PSI Blank 0 60 8HE 3H EZ 1HP 0 85 1 00 0 85 70 A DEL 150 PSI Blank 0 65 8HE 4L EZ 1HP 0 85 1 00 1 00 70 A DEL 150 PSI Blank 0 85 8HE 4H EZ 1HP 1 10 1 25 1 25 60 B DEL 150 PSI Blank 1 00 8HE 5L 99FRD N A 1 50 60 B HAGO 150 PSI Open 10 open 8HE 5H 99FRD N A 1 65 60 B HAGO 150 PSI Open 45 open RIELLO BURNER SPECIFICATIONS Boiler Model No Burner Model No Burner Series Nozzle Size Pump Pressur...

Страница 18: ...ide adequate ventilation Wear a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior to handling and removal by water misting the material and avoiding unnecessary disturbance of materials Wash work clothes separately from others Rinse washer thoroughly after use Discard RCF materials by sealing in ...

Страница 19: ...e on the boiler Boiler pressure should never be higher than 5 psi below the rating shown on the safety relief valve The valve rating can be found on the top of the safety relief valve Boiler temperature should never be higher than 250 F 4 Check for water leaks in boiler and system piping C WEEKLY MAINTENANCE WITH BOILER OPERATING 1 Flush float type low water cut off if used to remove sediment from...

Страница 20: ... in place 5 Replace jacket top panel 6 Inspect venting system G IF A LONG SHUTDOWN IS REQUIRED 1 To take boiler out of service if the boiler and system are not to be used when temperatures are below freezing a Drain the boiler and system completely and shut off make up water supply b Open main line power disconnect switch to boiler Remove the fuses or secure the switch so that the power cannot be ...

Страница 21: ...mber Jacket Depth A Jacket Width B Jacket Height C Rear of Jacket to c l of Vent D Vent Size Diameter E 8HE 3 14 1 8 22 1 8 35 7 1 16 6 8HE 4 18 1 8 22 1 8 35 9 1 16 6 8HE 5 22 1 8 22 1 8 35 11 1 16 7 Boiler Model Number Jacket Depth A Jacket Width B Jacket Height C Rear of Jacket to c l of Vent D 8HE 3 15 3 4 22 1 8 35 8 7 8 8HE 4 19 3 4 22 1 8 35 10 7 8 ...

Страница 22: ...Top venting only 1 Burner input based on No 2 fuel oil with a heating value of 140 000 Btu per gallon 2 Net water ratings based on an allowance of 1 15 3 Net steam ratings based on an allowance of 1 333 4 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements such as intermittent system operation extensive piping systems etc 5 Heating Capacity and...

Страница 23: ...et Front Steam 51800 9 Tankless Coil 8HE 3 Water 90637 Tankless Coil 8HE 4 8HE 5 Water 90534 Tankless Coil 8HE 3 8HE 4 Steam 90621 10 Flue Collector Plate Blanket Seal 90999 11 Flue Collector Cover Plate 8HE 3 90565 Flue Collector Cover Plate 8HE 4 90566 11A Top Outlet Flue Collector Plate 8HE 5 90562 12 Rope Seal 51209 13 Rear Outlet Cover Plate 90563 14 Flue Collar Adapter 8HE 3 8HE 4 Water 9056...

Страница 24: ...260 North Elm Street Westfield MA 01085 413 562 9631 FAX 413 562 3799 H ...

Отзывы: