20
MAINTENANCE
2. To thoroughly clean the boiler it must be brushed down
from the top. Alternatively, for limited space or minimum
clearance to combustible installations, cleaning the heat
exchanger from the combustion chamber side is
acceptable. If unit is extremely dirty, it may be necessary
to brush from both directions.
The target wall is made
of a soft ceramic fiber. Care must be taken not to
damage this material during cleaning.
3. Remove any scale or soot from the combustion
chamber area by vacuum cleaning or any other
available means.
4. Replace oil burner and flue collector cover plate
making sure all gaskets are in place.
5. Replace jacket top panel.
6. Inspect venting system.
G. IF A LONG SHUTDOWN IS REQUIRED
1. To take boiler out of service if the boiler and system
are not to be used when temperatures are below
freezing:
a. Drain the boiler and system completely and shut
off make-up water supply.
b. Open main line power disconnect switch to
boiler. Remove the fuses or secure the switch so
that the power cannot be turned on accidentally.
2. Be certain that the boiler and system are refilled
before returning to service.
Always keep the manual fuel supply
valve shut off if the burner is shut
down for an extended period of time.
CAUTION
All cover plates, enclosures, and
guards must be maintained in place
at all times, except during
maintenance and servicing.
NOTICE
Burner mounting plate must be
opened to facilitate this operation.
NOTICE