installation manual 

Evaluate the ceiling construction and please install with 

Ø

10 

hanging screw bolts. 

Keep indoor unit, outdoor unit, power supply wiring and 
transmission wiring at least 1 meter away from televisions 
and radios. This is to prevent image interference and 
noise in those electrical appliances. (Noise may be 
generated depending on the conditions under which the 
electric wave is generated, even if 1 meter is kept.) 

5.2   Install the main body 

There is enough room for installation and maintenance. 

The ceiling is horizontal, and its structure can endure the 
weight of the indoor unit. 

The outlet and the inlet are not impeded, and the 
influence of external air is the least. 

The air flow can reach throughout the room. 

The connecting pipe and drainpipe could be extracted out 
easily. 

There is no direct radiation from heaters. 

5.    INDOOR UNIT INSTALLATION 

5.1   Installation place 

(Refer to Fig.5-1,Fig.5-2 and Table 5-1 for specification.)

The indoor unit should be installed in a location that meets 
the following requirements: 

4.    INSPECTING AND HANDLING THE UNIT 

At delivery, the package should be checked and any damage should 
be reported immediately to the the service agent. 
 
When handling the unit, take into account the following: 

          Fragile, handle the unit with care. 
 
        Keep the unit upright in order to avoid compressor 
damage. 
 
Choose on before hand the path along which the unit is to be 
brought in. 
 
Move this unit as originally package as possible. 
 
When lifting the unit , always use protectors to prevent belt 
damage and pay attention to the position of the unit’s centre of 
gravity. 

CAUTION 

Fig.5-1

 

35mm

1000mm

 35mm

 35mm

Fig. 5-2

Please 

Refer to Fig.5-3

 and 

Fig.5-4 

for the hanging screw 

bolts distance 

The handling to the ceiling varies from the constructions, 
consult the construction person for the specific condition. 

Do keep the ceiling flat. Consolidate the roof beam 

to avoid

 

possible vibration. 

1     Installing Ø10 hanging screw bolts. (4 bolts) 

After the selection of installation location, position the refrigerant 
pipes, drain pipes,indoor & outdoor wires to the connection 
places before hanging up the machine.

Cut off the roof beam.

Strengthen the place that has been cut off, and 
consolidatethe roof beam.

The installation of hanging screw bolts. 

   

Fig.5-3                   

WOODEN CONSTRUCTION 

Roof beam

Hanging screw bolts

Ceiling 

Timber over the beam

Put the square timber traversely overthe roof beam, then install 
the hanging screw bolts.  

E. Connecting point of 

    refrigerant pipe

(D. gas side)

D. Connecting point of 

     refrigerant pipe

(E. Liquid side)

Drain point

Hook

Содержание Ceiling Type

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...ction of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical...

Страница 3: ...not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following circums...

Страница 4: ...me spare fittings please restore them carefully QUANTITY SHAPE NAME 5 Owner s manual 6 Installation manual 7 Remote controller manual 1 Remote controller on some models 2 Remote controller holder on s...

Страница 5: ...When handling the unit take into account the following Fragile handle the unit with care Keep the unit upright in order to avoid compressor damage Choose on before hand the path along which the unit...

Страница 6: ...Table 5 1 6 1 Installation Place 6 OUTDOOR UNIT INSTALLATION The outdoor unit should be installed in the location that meets the following requiements unit mm Fig 5 10 Fig 5 11 Fig 5 12 D Connecting...

Страница 7: ...outdoor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts a...

Страница 8: ...ODEL A B C D E H REMARK F 24 18 30 36 845 560 335 360 312 700 320 900 590 333 355 302 860 315 990 624 366 396 340 965 345 990 624 366 396 340 965 345 990 624 366 396 340 965 345 990 624 366 396 340 96...

Страница 9: ...6 15 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind Refer to Fig 6 15 NOTE NOTE Four different configuration are available for oudoo...

Страница 10: ...unit No Description Outdoor Unit Vibration proof rubber Anchor Bolt M10 Drainage Wide 100 Depth 150 Drainage Mortar Hole 100 Depth 150 Sling Bolt Suspension Bracket Table 6 4 Table 6 5 Fig 6 17 MODEL...

Страница 11: ...akage Please determine the torque according to Table 7 2 After the connecting work is finished be sure to check that there is no gas leak When connecting the flare nut coat the flare both inside and o...

Страница 12: ...rge hose with the vacuum pump Open the Lo lever of the manifold value completely Turn on the vacuum pump At the beginning of pumping loosen the maintenance nut of stop valve B a little to check whethe...

Страница 13: ...s position is shown figure below Drain Piping Fig 8 2 Fit the seal into the drain joint then insert the drain joint into the base pan hole of outdoor rotate 900 to securely assemble them Connect the d...

Страница 14: ...Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood c Whether any of the refrigerant is leaked A protection feature prevents the air conditioner...

Страница 15: ...1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Tabl...

Страница 16: ...0 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 5 Table 9 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30...

Страница 17: ...er wiring indoor Power linking wiring Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interf...

Страница 18: ...in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may cause damage The signs of th...

Страница 19: ...tallation manual QSDLI 016AEN The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 202000192522 20...

Страница 20: ...19 installation manual...

Страница 21: ...20 installation manual...

Страница 22: ...21 installation manual...

Страница 23: ...22 installation manual...

Страница 24: ...33...

Страница 25: ...34...

Отзывы: