AHI Carrier Ceiling Type Скачать руководство пользователя страница 12

11 

installation manual 

2.          Closing stop valve 

1. 

2. 

Remove the cap and turn the valve clockwise with the 
hexagon wrench. 

Securely tighten the valve until the shaft contacts the 
main bodyseal. 

Make sure to tighten the cap securely. 
For the tightening torque, refer to the table below. 

Table 7-3

Tightening torque N  M (Turn clockwise to close) 

Stop  

Valve size 

Shaft (valve body) 

Cap  

(Valve lid) 

Ø6.35 

Hexagonal  

wrench 4 mm 

Ø9.52 

Ø12.7 

Ø15.9 

Hexagonal  

wrench 6 mm 

Hexagonal  

wrench 6 mm 

Ø19 

Maintenance nut

35

40 

23

27 

18

22 

13.5

16.5 

5

7

9

11 

11

13 

11.5

13.9 

Additional Refrigerant Charge 

7.2 

Refrigerant cannot be charged until field wiring has been 
completed.

Refrigerant may only be charged after performing the leak 
test  and the vacuum pumping.

When charging a system, care shall be taken that its 
maximum permissible charge is never exceeded, in view of 
the danger of liquid hammer.

Charging with an unsuitable substance may cause 
explosions and accidents, so always ensure that the 
appropriate refrigerant is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes when 
charging refrigerant.

NOTE 

CAUTION 

If a negative result is gotten for R from Table 7-4, no 
refrigerant needs to be added nor removed. 

Additional refrigerant will be twice of R from Table 7-4 if 
the indoor unit installed throttle assembly.   
 

The outdoor unit is factory charged with refrigerant. Calculate 
the added refrigerant according  to the diameter  and  the 
length  of  the  liquid side pipe of the outdoor unit/indoor unit 
connection.(

suitable for throttle outdoor unit)

Fig.7-9

Using the vacuum pump 

Loosen and remove the maintenance nuts of stop valves A 
and B, and connect the charge hose of the manifold valve to 
the service port of stop valve A. (Be sure that stop valves A 
and B are both closed) 
 
Connect the joint of the charge hose with the vacuum pump. 
 
Open the Lo-lever of the manifold value completely. 
 
Turn on the vacuum pump. At the beginning of pumping, 
loosen the maintenance nut of stop valve B a little to check 
whether the air comes in (the sound of the pump changes, 
and the indicator of compound meter turns below zero). Then 
fasten the maintenace nut. 
 
When the pumping has finished, close the Lo-lever of the 
manifold valve completely and turn off the vacuum 
pump.Make pumping for 15 minutes or more and check that 
the compound meter indicates -76cmHg(-1X10 Pa) 
 
Loosen and remove the cap of stop valves A and B to open 
stop valve A and B completely, then fasten the cap. 
 
Disassemble the charge hose from the service port of stop 
valve A, and fasten the nut. 

Fig.7-8

Fig.7-7

Always use a charge hose for service port connection
After tightening the cap, check that no refrigerant leaks 
arepresent.

service port

cap

maintenance nut

Stop valve

Gas side

Liquid side

hexagon hole

shaft

seal

Outdoor

unit

Indoor

unit

CAUTION 

Pressure meter

Multi-meter

-76 cmHg

Lo-lever

Lo-lever

Charge hose

Charge hose

Vacuum pump

Hi-lever

Manifold valve

8.    CONNECT THE DRAIN PIPE 

Install the drainpipe of the indoor unit 

The outlet has PTI screw bread, Please use sealing materials 
and pipe sheath(fitting) when connecting PVC pipes.  

Table 7-4 

Liquid tube(mm) 

R410A R22 

Ø6.35 

Ø9.52 

Ø12.7 

Ø15.9 

Ø19                                                                                                              

0.022kg/m×(L-5) 

0.011kg/m×(L-5) 

0.060kg/m×(L-5) 

0.030kg/m×(L-5) 

0.110kg/m×(L-5) 

0.060kg/m×(L-5) 

0.170kg/m×(L-5) 

0.085kg/m×(L-5) 

0.250kg/m×(L-5) 

0.125kg/m×(L-5) 

0.030kg/m×(L-5) 

0.015kg/m×L 

0.065kg/m×(L-5) 

0.030kg/m×L 

0.115kg/m×(L-5) 

0.060kg/m×L 

0.190kg/m×(L-5) 

0.095kg/m×L 

0.290kg/m×(L-5) 

0.145kg/m×L 

orifice in the indoorunit   

orifice in the outdoorunit   

orifice in the outdoorunit   

orifice in the outdoorunit   

orifice in the outdoorunit   

orifice in the outdoorunit   

orifice in the indoorunit   

orifice in the indoorunit   

orifice in the indoorunit   

orifice in the indoorunit   

 

NOTE:The number of bends is up to the length of the max 
height drop.Usually for each 10m need a bend. 

NOTE:the table above refer to the liquid tube.

Содержание Ceiling Type

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...ction of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical...

Страница 3: ...not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following circums...

Страница 4: ...me spare fittings please restore them carefully QUANTITY SHAPE NAME 5 Owner s manual 6 Installation manual 7 Remote controller manual 1 Remote controller on some models 2 Remote controller holder on s...

Страница 5: ...When handling the unit take into account the following Fragile handle the unit with care Keep the unit upright in order to avoid compressor damage Choose on before hand the path along which the unit...

Страница 6: ...Table 5 1 6 1 Installation Place 6 OUTDOOR UNIT INSTALLATION The outdoor unit should be installed in the location that meets the following requiements unit mm Fig 5 10 Fig 5 11 Fig 5 12 D Connecting...

Страница 7: ...outdoor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts a...

Страница 8: ...ODEL A B C D E H REMARK F 24 18 30 36 845 560 335 360 312 700 320 900 590 333 355 302 860 315 990 624 366 396 340 965 345 990 624 366 396 340 965 345 990 624 366 396 340 965 345 990 624 366 396 340 96...

Страница 9: ...6 15 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind Refer to Fig 6 15 NOTE NOTE Four different configuration are available for oudoo...

Страница 10: ...unit No Description Outdoor Unit Vibration proof rubber Anchor Bolt M10 Drainage Wide 100 Depth 150 Drainage Mortar Hole 100 Depth 150 Sling Bolt Suspension Bracket Table 6 4 Table 6 5 Fig 6 17 MODEL...

Страница 11: ...akage Please determine the torque according to Table 7 2 After the connecting work is finished be sure to check that there is no gas leak When connecting the flare nut coat the flare both inside and o...

Страница 12: ...rge hose with the vacuum pump Open the Lo lever of the manifold value completely Turn on the vacuum pump At the beginning of pumping loosen the maintenance nut of stop valve B a little to check whethe...

Страница 13: ...s position is shown figure below Drain Piping Fig 8 2 Fit the seal into the drain joint then insert the drain joint into the base pan hole of outdoor rotate 900 to securely assemble them Connect the d...

Страница 14: ...Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood c Whether any of the refrigerant is leaked A protection feature prevents the air conditioner...

Страница 15: ...1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Tabl...

Страница 16: ...0 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 5 Table 9 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30...

Страница 17: ...er wiring indoor Power linking wiring Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interf...

Страница 18: ...in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may cause damage The signs of th...

Страница 19: ...tallation manual QSDLI 016AEN The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 202000192522 20...

Страница 20: ...19 installation manual...

Страница 21: ...20 installation manual...

Страница 22: ...21 installation manual...

Страница 23: ...22 installation manual...

Страница 24: ...33...

Страница 25: ...34...

Отзывы: