7.    INSTALL THE CONNECTING PIPE 

Check whether the height drop between the indoor unit and 
outdoor unit, the length of refrigerant pipe, and the number of 
the bends meet the following requirements:

(The number of the bends less than 15)

   The Procedure of Connecting Pipes 

7.1 

CAUTION 

All field piping must be provided by a licensed 
refrigeration technician and must comply with the 
relevant local and national codes. 

Do not let air, dust, or other impurities fall in the pipe 
system during the time of installation. 

The connecting pipe should not be installed until the 
indoor and outdoor units have been fixed already. 

Keep the connecting pipe dry, and do not let moisture in 
during installation. 

Execute heat insulation work completely on both sides 
of the gas piping and the liquid piping. Otherwise, this 
can sometimes result in water leakage. 

1. Suspend the unit as the drawing indicates. 

2. Ensure that ceiling can resist the Outdoor unit weight indicated  

    in specification label plate. 

Suspended unit 

No

    Description 

       Outdoor Unit 

 

      Vibration-proof rubber 

       Anchor Bolt M10 

       Drainage (Wide 100×Depth 150) 

       Drainage 

       Mortar Hole (

Φ

100×Depth 150) 

 

 

Sling Bolt 

Suspension Bracket 

Table 6-4

Table 6-5

Fig.6-17

MODEL 

B C 

1120 720 

1328 740 

1338 820 

1338 820 

18

24

30~36 

30~36 

48

60 






Table 7-1 

Drill a hole in the wall (suitable just for the size of the wall 
conduit), then set on the fittings such as the wall conduit and 
its cover. 
 
 
 

Model 

12K 

18K-24K 

30K-42K 

12K 

18K-24K 

30K-60K 

48K-60K 

12K 

18K-24K 

30K 

48K-60K 

36K 

50Hz T1 condition/R22 

Split type air conditioner

50Hz Vertical discharge air conditioner 

/60Hz T1 condition/R22 Split type air  

conditioner and Vertical discharge air  

conditioner 

The type of models

R410A inverter Split type air 

conditioner and and Centrifugal 

fan outdoor unit 

50 

50 

30  

15 

50 

30  

15 

30 

30 

25  

10 

25 

R410A Split type air conditioner 

and and Centrifugal fan outdoor 

unit 

50Hz/60Hz T3 condition 

(outdoor unit down)

50Hz/60Hz T3 condition 

(outdoor unit up)

the unit with quick joint

12K 

48K-60K 

18K-30K 

36K 

18K-24K 

42K-60K 

30K 

36K 

18K-24K 

12K-18K 

48K-60K 

42K 

30K 

36K 

50 

25  

15 

30 

50 

30  

25 

30 

25 

50 

30  

30 

50 

15 

35 

25  

20 

30 

25 

15  

20 

25 

15  

10 

20 

20 
25 

12  

15 

25 

10  

20 

10  

20 

refrigerant pipe 

The length of  

height drop 

The max  

Содержание Ceiling Type

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...ction of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical...

Страница 3: ...not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following circums...

Страница 4: ...me spare fittings please restore them carefully QUANTITY SHAPE NAME 5 Owner s manual 6 Installation manual 7 Remote controller manual 1 Remote controller on some models 2 Remote controller holder on s...

Страница 5: ...When handling the unit take into account the following Fragile handle the unit with care Keep the unit upright in order to avoid compressor damage Choose on before hand the path along which the unit...

Страница 6: ...Table 5 1 6 1 Installation Place 6 OUTDOOR UNIT INSTALLATION The outdoor unit should be installed in the location that meets the following requiements unit mm Fig 5 10 Fig 5 11 Fig 5 12 D Connecting...

Страница 7: ...outdoor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts a...

Страница 8: ...ODEL A B C D E H REMARK F 24 18 30 36 845 560 335 360 312 700 320 900 590 333 355 302 860 315 990 624 366 396 340 965 345 990 624 366 396 340 965 345 990 624 366 396 340 965 345 990 624 366 396 340 96...

Страница 9: ...6 15 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind Refer to Fig 6 15 NOTE NOTE Four different configuration are available for oudoo...

Страница 10: ...unit No Description Outdoor Unit Vibration proof rubber Anchor Bolt M10 Drainage Wide 100 Depth 150 Drainage Mortar Hole 100 Depth 150 Sling Bolt Suspension Bracket Table 6 4 Table 6 5 Fig 6 17 MODEL...

Страница 11: ...akage Please determine the torque according to Table 7 2 After the connecting work is finished be sure to check that there is no gas leak When connecting the flare nut coat the flare both inside and o...

Страница 12: ...rge hose with the vacuum pump Open the Lo lever of the manifold value completely Turn on the vacuum pump At the beginning of pumping loosen the maintenance nut of stop valve B a little to check whethe...

Страница 13: ...s position is shown figure below Drain Piping Fig 8 2 Fit the seal into the drain joint then insert the drain joint into the base pan hole of outdoor rotate 900 to securely assemble them Connect the d...

Страница 14: ...Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood c Whether any of the refrigerant is leaked A protection feature prevents the air conditioner...

Страница 15: ...1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Tabl...

Страница 16: ...0 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 5 Table 9 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30...

Страница 17: ...er wiring indoor Power linking wiring Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interf...

Страница 18: ...in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may cause damage The signs of th...

Страница 19: ...tallation manual QSDLI 016AEN The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 202000192522 20...

Страница 20: ...19 installation manual...

Страница 21: ...20 installation manual...

Страница 22: ...21 installation manual...

Страница 23: ...22 installation manual...

Страница 24: ...33...

Страница 25: ...34...

Отзывы: