Mini Merlin Installation, Operation & Maintenance                                                                                                                              

 

Rev: 03 05-22 

11  

Alarm Reset 

 
To reset after an alarm - press the touch sensor once.  
If the device enters an alarm state at any time, the gas level indicator will remain red to alert the user that a 
high/dangerous level of gas has been detected, until the device is reset. 

 

 

 

Remote Shut Off Indication 

 
A message will display if the device is integrated with remote shut off devices such as smoke or fire alarms etc. When 
activated, the device will isolate the gas supply if configured to do so. The mini merlin would need to be reset once 
any issues have been investigated and rectified. 

 

Manual Circuit Simulation Test 

 

The manual circuit test does not check the gas sensor itself!  

 
Press and hold the touch sensor during normal operation.  
This option gives the user the opportunity to test each relay/output in response to gas. 
 
 

When the touch button is pressed and held during normal operation the mini merlin will simulate an open circuit to 
ensure all configured systems, outputs, alarms, indications, and other external devices operate as intended in 
response to gas.  

 

End of Operational Life (EOL) 

 

The EOL is approximate from the first five (5) hours of continuous power! 

 

The EOL will depend on the type of gas your detector is targeting and may vary depending on its application and 
environmental conditions such as the frequency of exposure to the target gas, poisons, or inhibitors! 

 
The typical life of a gas detector depends on its application and intended target gas, in addition the operational life 
can be prolonged if the system and equipment is installed and maintained in accordance the instructions stated within 
this manual.  
 
At the end of its predicted operational life 

 

the detector will display an ‘End of Life’ 

indication on screen. This 

message indicates that the detector has reached its expected operational lifecycle and no gas levels are displayed. 
You must contact your supplier immediately for replacement.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание Mini Merlin LPGCO v2-FL

Страница 1: ...O v2 FL Dual Gas Detector Installation Operation Maintenance Manual Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this...

Страница 2: ...uits 8 Wiring Adaptable Outputs 8 Wiring Pilot Water Heater Boiler Limit Breaker 9 Wiring Remote Shut Off 9 Auto Reset Buzzer Switches 9 Building Management System 10 Operation 10 Initial Power Up 10...

Страница 3: ...ic medical conditions If in doubt consult a doctor physician Your product should reach you in perfect condition if you suspect it is damaged contact your supplier Warranty Statement Warranty Coverage...

Страница 4: ...used for heating cooking and vehicles It is Obtained during the processing of crude oil or direct from the sea Colourless and odourless An odourising agent is added before distribution Half as heavy a...

Страница 5: ...ted in positions determined by those who have knowledge of gas dispersion the process plant system and equipment involved and in consultation with both safety and electrical engineering personnel Take...

Страница 6: ...electrical box Restrain the hazardous live wiring from accidental loosening to prevent wires from moving after installation and touching parts of opposite polarity or at low voltages Isolate the equi...

Страница 7: ...than connected Heat detectors use wires suitable for at least 167 F 75 C Wiring Gas Solenoid Valve When the installation includes a standing pilot ensure the internal auto reset dip switch is in the O...

Страница 8: ...iance Multiple appliance limit switches can be wired in series Wiring Adaptable Outputs The mini merlin can be used to effect external relays and contactors to disable multiple appliances when a fault...

Страница 9: ...mally closed and will alarm when energised open isolating the gas supply When using this input only the mains utility output shall de energize If you are using the CO or NG relay to shut down a boiler...

Страница 10: ...he touch sensor on the front cover for 3 seconds The detector enters a stabilisation phase for approximately one minute during this period the device is not operational If the detector has been config...

Страница 11: ...h button is pressed and held during normal operation the mini merlin will simulate an open circuit to ensure all configured systems outputs alarms indications and other external devices operate as int...

Страница 12: ...briefly exposing the unit to a known concentration of the target gas that usually exceeds the highest alarm point If the detector goes into alarm and all signals outputs activate then the system is w...

Страница 13: ...ylinder All cylinders will re seal upon removal of the regulator valve Deviating from this test process is deemed improper and may affect the functional safety of your device Exposure to chemicals smo...

Страница 14: ...ne LPG LEL Batch Cylinder No CO ppm Batch Cylinder No Propane LPG LEL Batch Cylinder No CO ppm Batch Cylinder No Propane LPG LEL Batch Cylinder No CO ppm Batch Cylinder No Propane LPG LEL Batch Cylind...

Страница 15: ...3 15A 250Vac Equipment Overvoltage Category II Pollution Degree 2 Relays Volt Free BMS relay output 0 5A switching current resistive load Environmental Ingress Protection Not Formally Evaluated Opera...

Страница 16: ...nded and is free from any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however AGS can assume no responsibility for any errors or omiss...

Отзывы: