Fig. 4: Level meter dead zone
m = Dead zone
A = reference plane for the measurement
Fig. 5: Distance from the tank wall
d = Distance from the tank wall
c = Maximum reach of the level meter
Installation in closed containers
When installing in closed containers, the sensor face must not be flooded. Use a pipe socket if the
distance cannot be maintained in any other way.
Fig. 6: Possible installation in the container
a = Height of pipe socket
b = Wide pipe socket
m = Dead zone (Incorrect
measurement)
UST 20-01, -11
a < 3 b
b > 100 mm
UST 20-21
a < 1,5 b
b > 100 mm
UST 20-31
a < 1,5 b
b > 150 mm
Vessel installations
Vessel installations can cause strong false echoes that are superimposed over the useful echo
signals (roughness on container walls, various partitions, agitator etc.) It is necessary to map false
reflections by activating the mode "TEACHING".
In case of installed mixers, it is necessary to put the mixers to position under the level meter (di-
rect the agitator paddle to the ultrasonic signal beam).
A