Technical specifications
– English –
16
TAS 03
4
Technical specifications
Fig. 6: Dimensions
Table 4: Technical specifications
Parameter
Value
General specifications
Operating pressure
Max. 10 bar
Blow-off capacity
2.4 m³/h at 110 °C and
Δ
p =1 bar
Connections
2 x G¾ female thread
Connection pocket
G½ male thread
Length capillary tube
1300 mm
4000 mm
Length pocket
160 mm
Installation length in boiler
146 mm
Operating medium
Water