Mounting
– English –
20
TAS 03
If the cross section of the discharge line is greater than or equal
to DN 25, the maximum length of the discharge line is 4 m and
the maximum number of elbows is 3.
The end of the discharge line must be approx. 20 … 40 mm
above the drain outlet; the following conditions apply: observa-
ble, free, protected against pollution, frost-protected, perma-
nently installed. If you use a funnel, the outlet of the funnel must
have a cross section of at least DN 40.
4.
If the TAS 03 screw connection is used, the PTFE sealing ring
must be screwed into the valve housing.
5.
Unscrew the locking screw, pull out the probe system and screw
the pocket into the appropriate socket so that it is sealed.
CAUTION
Only use the pocket shipped with the product.
6.
Refit the probe system and secure it with the locking screw.
7.
Perform a function test: Press down the pressure cap.