Mounting and commissioning
28
LAG-14 ER
In the case of greater distances, mount a cable junction box with de-
gree of protection IP 55 next to the top of the black LAG container.
Make sure the probe can easily be removed from the container for
the leak detection fluid for function tests. Do not shorten the signal
cable.
Use control cables with 2 x 1 mm² with blue cable jacket for in-
trinsically safe current circuits to extend the signal cable. Use
shielded cable at lengths of 5 m and more.
The total length of the signal cable must not exceed 50 m. Use
underground cables such as NYY 2 x 1.5 mm² for underground
cable installation.
Do not route intrinsically safe circuits and circuits that are not in-
trinsically safe in the same cable duct. Observe VDE 0165 and
all other regulations applicable at the installation site.
Do not route the signal cable next to mains cables; danger of in-
terference.
Protect the signal cable from damage; use a metal pipe, if re-
quired.
Route the signal cable from the probe through the left cable
gland into the control unit and connect it to the blue two-pole ter-
minal with the designation "Probe" in the control unit. You do not
have to ensure a specific polarity.
No more than two black LAG containers with one probe each may be
connected in series to one control unit.
Output
The output signal of the leak detector is made available via a volt-
age-free relay contact (normally open contact). The relay contact is
fused with a 2 A fuse (slow-blow).