Carry out work in the machine area only, if AC and/or DC supplies are switched
off. Switched off output stages or controller
enabling’s are no suitable means of
locking. In the case of a malfunction the drive may accidentally be put into
action.
This does
not apply to drives with the special “Safe Stop” feature in accordance
with EN 954-
1 CAT 3 or with the “Safe Torque Off” feature in accordance with
EN 61800-5-2. This feature can be achieved with the SE-Power FS by
integrating the module SE-Power FS Safety Module STO for example.
Initial operation must be carried out with idle motors, to prevent mechanical
damages for example due to the wrong direction of rotation.
Electronic devices are never fail-
safe. It is the user’s responsibility, in the case
an electrical device fails, to make sure the system is transferred into a secure
state.
The servo positioning controller and in particular the brake resistor, externally or
internally, can assume high temperatures, which may cause serious burns.
Protection against contact with electrical parts
This section only concerns devices and drive components carrying voltages exceeding 50 V.
Contact with parts carrying voltages of more than 50 V can be dangerous for people and may
cause electrical shock. During operation of electrical devices some parts of these devices will
inevitably carry dangerous voltages.
DANGER!
High electrical voltage!
Danger to life, danger due to electrical shock or serious personal injury!
The appropriate DIN, VDE, EN and IEC regulations as well as all national and local safety
regulations and rules for the prevention of accidents apply for the assembly and maintenance
of the system. The plant engineer or the operator is responsible for compliance with these
regulations:
Before switching on the device, install the appropriate covers and protections
against accidental contact. Rack-mounted devices must be protected against
accidental contact by means of housing, for example a switch cabinet. The
national regulations for safety/accident prevention must be complied with!
Always connect the ground conductor of the electrical equipment and devices
securely to the mains supply. Due to the integrated line filter the leakage current
exceeds 3.5 mA!
Comply with the minimum copper cross-section for the ground conductor over its
entire length (see for example EN 60800-5-1).