B.2.6.6 The «Set point < » and «Set point > » columns at the «Measured parameters» table re-
flects the transducer configuration to be sent to the AED indication device nominal value. The default
reduction set point is 0,1 relating to the nominal value of the measurand. The default growth set point
is 1,1 relating to the nominal value of the measurand.
When the measurand is less than set point, the « < » sign is indicated rightwards of the indicat-
ing value.
When the measurand is more than set point, the « > » sign is indicated rightwards of the indicat-
ing value.
When the measurand is between set points, the signs aren’t indicated.
B.2.6.7 To edit set points of measurand open the «Property» dialog box. To open Property dialog
box, select and double-click the left mouse button on editing parameter in the «Measured parameters»
area.
Edit set points at the «Property» area. Enter the reduction set point at the «Set point < » area using,
the relevant measurement unit. Enter the growth set point at the «Set point > » area, using the relevant
measurement unit. The form of the property dialog box for phase current is given in Figure B.7