2.3.3 The transducer must be configured according with table 11.
Table 11
Name and nomenclature
Value and meaning
Password for configuration
12345
Data exchange parameters by RS-485(1) and RS-485(2):
- baud rate, bps
- stop bit quantity
- parity
- device code
- communication protocol
- memory cell size (byte)
9600
2
NO
1
MODBUS ASCII
2
Measurement mode (3 or 4-wire system)
4-wire system
Measurement parameters
Registers address
Register size, byte
Resolution factor for every measurand
k
1
k
2
k
3
group ID
In according with
47113964.505100-01 90 03-1
2
5000
5000
50000
1
2.3.4 Before the mounting of the transducer at the object it is necessary to set requiring configu-
ration by «SetComplex 3.1 (EN)».
A computer for this purpose has to meet following minimum system requirements:
- Windows 9x/NT/XP/Vista/7;
- Pentium 100 Processor or higher;
- 32 MB RAM;
- SVGA video adapter;
- USB interface ;
- CD-ROM.
Before the connection of the transducer unstick the protection sticker from the cover. .
To be configuration is authorized apply only valid password. The default password of the
transducer is «12345»
«SetComplex 3.1 (EN)» description is presented in the Annex B.
If it isn’t assumed to use the interface RS-485(2) after configuration, the protective patch
should be placed on the transducer front panel.
2.3.5 The transducer enables to transfer the measurement data to the external indication device (sup-
plied on separate request).
- AED is the seven-segment display indication device. It indicates three selected parameters and set
points (30 devices into one transducer maximum).
- AEGD is the indication device performed on the graphic display. It indicates three snapshots with
eight selected parameters alternately.
The external indication device image the data by way of four-digit decimal number which corres-
ponded to measurand expressed in measurement unit. The transformer ratio of the external current and
voltage transformers is taken into account. The updating rate of data is 3 Hz.
Transferring of the measurement data to the external indication device is carried out by the RS-
485(2) interface with applying of the «ExtDev» communication protocol.