background image

- 22 -

Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection of
refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

Leak detection methods

The following leak detection methods are deemed acceptable for systems containing flammable
refrigerants.

Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not 
be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-
free area.).  Ensure that the detector is not a potential source of ignition and is suitable for the 
refrigerant used. Leak detection equipment shall be calibrated to the refrigerant employed and the 
appropriate percentage of gas (25 % maximum) is confirmed. 

Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing 
chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-
work. 

If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered 
from the system, or isolated (by means of shut off valves) in a part of the system remote from the 
leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during 
the brazing process. 

Removal and evacuation

When breaking into the refrigerant circuit to make repairs or for any other purpose. Conventional
procedures shall be used. However, it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to: 

. Remove refrigerant 
. Purge the circuit with inert gas 
. Evacuate 
. Purge again with inert gas 
. Open the circuit by cutting or brazing. 

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be 
"flushed" with OFN to render the unit safe. This process may need to be repeated several times. 
Compressed air or oxygen shall not be used for this task. 

Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until 
the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. 
This process shall be repeated until no refrigerant is within the system. 

When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 
place. 

Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation 
available working on them. 

--

Automated Environmental Systems Ltd., Unit 1, 1 Wimbledon Avenue, Brandon, Suffolk IP27 0NZ

01842 819130 | [email protected] 

Содержание Remora Mini

Страница 1: ...POOL HEAT PUMP MANUAL Remora Mini Swimming Pool Heat Pump 1 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co u...

Страница 2: ...12 6 4 Parameter checking and adjustment 15 7 SYSTEM PROTECTIONS ERROR CODES 17 8 MAINTENANCE AND INSPECTION 19 9 WIRING DIAGRAM ELECTRICAL CONNECTION 25 9 1 Wiring diagram 25 9 2 Electrical connecti...

Страница 3: ...manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperat...

Страница 4: ...ance shall be installed in accordance with national wiring regulations Before obtaining access to terminals all supply circuits must be disconnected Spaces where refrigerant pipes shall be compliance...

Страница 5: ...r the use of harmful substances in electric and electronic devices 4 The unit CANNOT be installed near the flammable gas Once there is any leakage of the gas fire can occur 5 Make sure that there is c...

Страница 6: ...s are found inside the box Carton Box Item Image Quantity Swimming pool heat pump 1 Operation and Installation Manual 1 Winter Cover 1 Accessories 1 Set Automated Environmental Systems Ltd Unit 1 1 Wi...

Страница 7: ...emora m3 Remora m5 Remora m7 A 647mm B 480mm C 98mm D 257mm E 530mm F 506mm G 180mm H 102mm Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales au...

Страница 8: ...14 Wired controller 5 Fan blade 15 Electrical control box 6 Fan motor 16 Compressor 7 Evaporator 17 4 way valve 8 Titanium heat exchanger 9 Liquid separator Not available for mini units 10 EEV Not ava...

Страница 9: ...The controller could be mounted on the wall 5 2 Swimming Pool Heat Pumps Location The unit will perform well in any outdoor location provided that the following three factors are presented 1 Fresh Air...

Страница 10: ...can be run straight into the unit Location Connect the unit in the pool pump discharge return line downstream of all filter and pool pumps and upstream of any chlorinators ozonators or chemical pumps...

Страница 11: ...y to or from the pool water Grounding the unit is still required to protect you against short circuits inside the unit 5 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or sp...

Страница 12: ...DIGITAL CONTROLLER GET WET THIS MAY CAUSE AN ELECTRIC SHOCK OR FIRE NEVER PRESS THE BUTTONS OF THE DIGITAL CONTROLLER WITH A HARD POINTED OBJECT THIS MAY DAMAGE THE DIGITAL CONTROLLER NEVER INSPECT OR...

Страница 13: ...s press and to set temperature in current mode Timer button Press this button to enter into Timer ON OFF setting mode combing with and buttons to set 2 groups of Timer ON OFF Hold for 5 seconds to acc...

Страница 14: ...setting Timer 1 ON minute digit press again to enter into Timer 1 OFF hour digit the setting way is same as above When finish setting Timer OFF time press again to confirm current Timer settings and e...

Страница 15: ...it turns off to cancel defrost Remove error history record On error history query interface screen press and for 5 seconds to remove error history records Reset Under unit OFF status press and for 5 s...

Страница 16: ...of the compressor 10 15 Heat 10 25 Cool A3 Compressor exhaust gas temp Refrigerant gas temperature at the outlet of the compressor 40 80 Heat 60 95 Cool A4 Ambientairtemp Surrounding ambient air temp...

Страница 17: ...to set water temperature 28 in heat mode for instance If this parameter is set to 2 heat pump won t restart until water temperature drops to 26 1 5 2 L3 Heat Mode Water Temp Set Set target water temp...

Страница 18: ...re switch failure 7 Main PCB damaged 1 Check pump and water control valve 2 Discharge and then recharge the refrigerant 3 Discharge some refrigerant 4 Set lower water temp 5 Reconnect the switch 6 Rep...

Страница 19: ...ce the sensor 3 Replace the main PCB Er29 Compressor suction gas temp sensor failure 1 Sensor open circuit 2 Sensor short circuit 3 Main PCB damaged 1 Check the sensor connection 2 Replace the sensor...

Страница 20: ...mable refrigerants safety checks are necessary to ensure that the risk of ignition is minimised Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a fla...

Страница 21: ...all be followed If in doubt please consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants a The charge size...

Страница 22: ...ly Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with...

Страница 23: ...itrogen OFN shall then be purged through the system both before and during the brazing process Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpos...

Страница 24: ...t release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not...

Страница 25: ...ess it has been cleaned and checked Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants...

Страница 26: ...iring diagram Please refer to the wiring diagram on the electric box Models Remora m3 Remora m5 Remora m7 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 8...

Страница 27: ...26 9 2 Electrical connection Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Страница 28: ...e power and installation requirements Please refer to table below Heat Pump Model Cable Size Remora m3 Remora m5 Remora m7 3 x 1 5mm2 The above are for references only Please refer to qualified electr...

Страница 29: ...28 NOTES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Страница 30: ...29 NOTES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Страница 31: ...30 NOTES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Отзывы: