background image

Installation, Operation & Maintenance Manual

IM-225

14

Maintenance

These motors use brushless technology with sealed bearings so no maintenance is required other than keeping the motors dry 

and free of dirt, dust and debris. Always keep records of the maintenance that is performed.

Troubleshooting

Remote Dial does not vary the motor speed (all motor types, except OP)

•  Verify that correct connections are made (refer to pages 9-10).

•  Make sure that the connections are solid.

•  Check control input voltage at connection (inside transformer box).

•  Make sure that the dial on the motor is opened CW.

Speed control does not vary the motor speed

•  Check voltage to ensure the motor is receiving the correct input voltage.

•  Check voltage at the remote dial. 12V AC should be present across the 12V and COM terminals and 0-10V DC should be present 

between the 0-10V and COM terminals.

•  Verify that the potentiometer or 0-10V DC lead is properly wired to the control board according to the diagram.

•  Verify that all of the connections inside of the fan and motor are secure.

GridPoint controller does not connect to motor

•  Check that cable connections are secure between the motor and the GridPoint controller.

Motor does not operate (TEFC motors:

 67002107, 67002205

)

•  Check that the motor is wired for the correct supply voltage.

•  Verify the Status LED is solid red.

•  Verify that the jumper wire is present between terminals 9 and 10 on the low voltage terminal board because this is required 

for the motor to operate.

•  Verify that the yellow wires are present on terminals 5 and 6 on the low voltage terminal board.

Fault indication (TEFC motors: 

67002107, 67002205

)

A red LED is located either on the control board or on the side of the conduit box to 

provide diagnostic assistance of motor faults. When a fault occurs, the LED will blink 

a specific number of times to identify the fault that has occurred. See the table to the 

right for fault indications.

When a fault occurs, the LED will blink the number of times corresponding to the fault, 

pause and then repeat blinking. Count the number of blinks multiple times to ensure 

that the proper fault has been identified. With most of the faults, the motor will restart 

automatically. If the motor experiences an overload fault over 10 times within an hour, 

the motor will shut down to protect itself and the power will need to be reset.

TEFC Motors (67002107 and 67002205)

No. of 

Blinks

Indicated Fault

2

Overcurrent

3

Overvoltage

4

Undervoltage

5

Communication Error

6

Sync Loss

7

Spin Fault

8

3 Sec/60 Sec

Motor Overload

9

Motor Over-Temperature

Содержание ACXD

Страница 1: ...afety practices and read this manual It is the user s responsibility to make sure that all requirements of good safety practices and any applicable safety codes are strictly adhered to Because of the wide variety of equipment covered in this manual the instructions given here are general in nature Additional product and engineering information is available at www aerovent com REVIEW AMCA BULLETIN ...

Страница 2: ...protection respiratory equipment hand and foot protection when installing or servicing the fan Always use caution when entering a fan s air path High velocity airflow can cause you to lose your balance Motors can be hot and similarly if the fan is subject to processes that are hot the fan housing could be hot Fans are often used to move hazardous materials that could be dangerous Always wear prote...

Страница 3: ... as shown Lifting lugs are provided on most units 1 Maintain handling equipment to avoid serious personal injury and do not stand under the load 2 If supplied only use the provided lifting lugs to lift the equipment 3 Ensure that the lifting equipment is rated for the capacity to be lifted CAUTION Partial or disassembled units require special handling All parts should be handled in a method that p...

Страница 4: ... of authorities having jurisdiction and all applicable codes This equipment is to be installed by an experienced installation company and fully trained personnel Verify that the impeller rotation is correct It should be CW when viewed from the shaft end CCW from opposite shaft end Refer to IM 995 IM 4050 IM 4205 or IM 4800 for detailed installation instructions on the fans that utilize EC motors D...

Страница 5: ...ections See Maximum RPM tables on page 8 for maximum allowable RPM for fan motor combinations 1 Motor Mounted Dial MMD Standard Feature A potentiometer is mounted to the motor housing offering full speed control range Speed adjustment is made with a small flat head screwdriver With this option the motor s 0 10V DC control leads are terminated in a standard 2x4 junction box from the factory and can...

Страница 6: ...Power Connect and Direction LEDs will be on 4 If the Up arrow is pressed the display will show E000 no error max speed constant speed d000 direction and C000 motor operation mode 0 5 To set the maximum speed a Press SET for 2s b Press the Up or Down arrow to display P000 c Press OK This will display the current maximum speed d Press the Up or Down arrow to change the digit To move to the next digi...

Страница 7: ...he motor operates off of a 2 10V DC signal it will be off when a 0 1 9V DC signal is present If the user requires the remote mounted dial to turn off the motor the dial should be set at 0 10V DC The field supplied 3 wire control cable connections from the transformer box to the remote mounted dial must be made as shown in table to the right The user should verify that the dial is properly working ...

Страница 8: ...4 1800 1800 098 1 4 1800 1800 110 1 4 1800 1800 112 1 4 1800 1800 122 1 2 1800 2205 124 1 2 1800 1800 135 3 4 1800 1800 140 3 4 1800 1800 150 2 1800 1800 157 2 1800 1800 165 2 1800 1800 194 1 1200 1400 Maximum RPM Tables SCDD Size Motor HP Motor RPM Max Fan RPM 080AE 1 4 1800 1800 090AE 1 4 1800 1800 100AE 1 2 1800 1800 120AE 3 4 1800 1800 135AE 1 1800 1800 150AE 1 1200 1200 165AE 1 1200 1200 135A...

Страница 9: ...HITE FACTORY PROVIDED FIELD INSTALLED Note Diagram refers to motors 67001001 67001003 67001004 67001005 67001008 67001105 Figure 2 Remote Mounted Dial Wiring Diagram 208 230VAC Single Phase FIELD INSTALLED FACTORY PROVIDED WHITE BLACK GROUND DISCONNECT BOX RED WHITE BLACK MOTOR POWER LEADS CONTROL LEADS SIGNAL GROUND WHITE BLACK 24 VAC 0 10 V COM BLUE YELLOW 208 VAC RED 230 VAC ORANGE 1 3 2 REMOTE...

Страница 10: ...gle Phase 24 VAC REMOTE DIAL TCF 2 3 1 115 OR 230 VAC YELLOW BLUE COM 0 10 V 24 VAC BLACK WHITE GROUND SIGNAL CONTROL LEADS POWER LEADS MOTOR BLUE YELLOW DISCONNECT BOX GROUND BLACK WHITE FACTORY PROVIDED FIELD INSTALLED 0 10V IN 0 10V COM Note Diagram refers to motors 67001701 67001703 67001704 67001705 67001715 ...

Страница 11: ...14 AWG Tighten to 5 7 in lb L2 L1 N Table 1 Single Phase Power Requirements Note Internally the Speed Controller provides 240VAC 3 phase at 8kHz switching frequency to the motor Table 2 Branch Protection Note A different fuse Class may be used as an alternative to the Class shown provided it is of the same or lesser rating and has equivalent or better clearing time and peak let through characteris...

Страница 12: ... as follows a Connect a positive voltage source to pin P10 2 Analog Input b Connect source common to P10 3 DGND Use only Copper Wire for all wiring It is the responsibility of the installer controls engineer to ensure that any field suppliedcontrolsarecompatibleandfunctionalwiththismotortechnology Aerovent is not responsible for field supplied or customer designed fan or motor controls 3 Verify ro...

Страница 13: ...to connect the three phase AC lines and earth ground to their supply Motor Part Numbers HP Voltage Phase 67003305 1 208 230 3 67003306 11 2 208 230 3 67003307 2 208 230 3 67003309 3 208 230 3 67003405 1 460 3 67003406 11 2 460 3 67003407 2 460 3 67003409 3 460 3 Speed Control Options OP Motors Operation Method This engineering sample is setup for constant speed operation The analog DC control volt...

Страница 14: ...roller Motor does not operate TEFC motors 67002107 67002205 Check that the motor is wired for the correct supply voltage Verify the Status LED is solid red Verify that the jumper wire is present between terminals 9 and 10 on the low voltage terminal board because this is required for the motor to operate Verify that the yellow wires are present on terminals 5 and 6 on the low voltage terminal boar...

Страница 15: ...Installation Operation Maintenance Manual IM 225 15 Date Completed Maintenance Performed By Comments Model Number__________________________ Serial Number __________________________ Fan Maintenance Log ...

Страница 16: ...WWW AEROVENT COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7500 Fax 763 551 7501 2017 2022 Aerovent ...

Отзывы: