f. Outdoor Dependent Supply or Extract Air Temperature Control
If the outside temperature is below the adjustable limit (winter), outdoor compensated supply air temperature control will be
active (see b). Otherwise (summer) the Cascade Extract Air Control (see d) is active.
g. Outdoor Compensated Room Temperature Control
Note: Only available with KWL-FTF accessory. Connection of the analog output A2 (temperature signal) of the KWL-FTF to the
analogue input AI2 at the controller.
The room temperature can be adapted when the outside temperature rises. For example, at higher outside temperatures a
slightly higher room temperature may be acceptable or a slightly lower in cooler weather conditions. This temperature control
mode is used to conserve energy.
Control function
↑
Mode
->
Extract/Supply air ->
↓
Supply air temp
↑
Setp: XX.X
°C
↓
Extract air temp
↑
Setp: XX.X
°C
↓
Outdoor temp for
↑
Control mode change
XX.X
°C
↓
Содержание EVO-R
Страница 1: ...EVO R COMPACT AIR HANDLING UNIT WITH ROTARY HEAT RECOVERY ...
Страница 129: ...129 Fig 170 Fig 171 ...
Страница 130: ...130 Fig 171 ...
Страница 132: ...132 Fig 173 Fig 174 ...
Страница 133: ...133 Fig 174 ...
Страница 135: ...135 Fig 176 Fig 177 ...
Страница 136: ...136 Fig 177 ...
Страница 138: ...138 Fig 179 Fig 180 ...
Страница 139: ...139 Fig 180 ...
Страница 141: ...141 Fig 182 Fig 183 ...
Страница 142: ...142 Fig 183 ...
Страница 144: ...144 Fig 185 Fig 186 ...
Страница 145: ...145 Fig 186 ...
Страница 147: ...147 Fig 188 Fig 189 ...
Страница 148: ...148 Fig 189 ...
Страница 150: ...150 Fig 191 Fig 192 ...
Страница 151: ...151 Fig 192 ...
Страница 153: ...153 Fig 194 Fig 195 ...
Страница 154: ...154 Fig 195 ...
Страница 155: ...155 ...