COMMISSIONING - WARNINGS

COMMISSIONING - WARNINGS

Please note that, on request by the Aermec customer or the legitimate 

owner of the machine, the units in this series can be started up by the 

AERMEC After-Sales Service in your area (valid only on ITALIAN territory). 

The start of operation must be scheduled in advance based on the time 

frame for the completion of works for the system. Prior to the intervention, 

all other works (electrical and hydraulic hook-ups, priming and bleeding of 

air from the system) must have been completed.

START-UP

OPERATIONS TO BE PERFORMED WITH NO VOLTAGE PRESENT

 ATTENTION 

the unit is not working:

Check:

-  All safety conditions have been respected

-  The unit is correctly fixed to the support surface

-  The minimum technical spaces have been respected 

-  That the main power supply cables have appropriate cross-section, 

which can support the total consumption of the unit. (see electric data 

sections) and that the unit has been duly connected to the ground.

-  That all the electrical connections have been made correctly and all 

the terminals adequately tightened.

OPERATIONS TO BE PERFORMED WITH THE UNIT LIVE

 

ATTENTION 

the unit is still not working:

-  Supply power to the unit by turning the main switch to the ON 

position.

-  Use a tester to check that the value of the supply voltage to the 

U.V.W. phases lies within the tolerance range, and also check that the 

unbalance between the phases does not exceed 3%.

-  Check that the connections made by the installer are in compliance 

with the documentation.

-  Verify that the resistor of the compressor sump is working by 

measuring the increase in temperature of the oil pan. The resistance/s 

must function for at least 12 hours before start-up of the compressor 

and in any event, the temperature of the oil pan must be 10-15°C 

higher than room temperature.

HYDRAULIC CIRCUIT CONTROLS

-  Check that all hydraulic connections have been made correctly, that 

the information on the plates has been observed and that there is a 

filter upstream of the entire WWM line. 

(Mandatory component for 

warranty to be valid).

-  Make sure that the circulation pump/s is operating and that the water 

flow rate is sufficient to close the contact of the flow switch, if installed.

-  Check the water flow rate, measuring the pressure difference between 

inlet and outlet of the evaporator and calculate the flow rate using the 

evaporator pressure drop tables present in this manual.

-  Check the correct functioning of the flow meters if installed. Closing 

the cut-off valve at the output of the heat exchanger; the unit control 

panel must show the block. Finally re-open the valve and rearm the 

block

COMMISSIONING

-  Once all the aforementioned checks have been carried out, the unit 

can be commissioned

-  Close the door of the electrical panel.

-  Set the unit main switch to ON, the unit will start after a few minutes

OPERATIONS TO BE PERFORMED WITH MACHINE ON

 ATTENTION 

the unit is working:

Check:

-   That the compressor input current is lower than the maximum 

indicated in the electrical data table.

-   Before starting the unit, check that the compressor rotates in the 

correct direction through a three-phase protection. The spiral 

compressors compress in one direction of rotation only. Therefore, it 

is essential for the phase of the three-phase spiral compressors to be 

correctly connected (the correct direction of rotation can be controlled 

when the pressure on the intake side decreases and that on the flow 

side increases with the compressor in operation). If the connection is 

incorrect, the direction of rotation is reversed: this causes a loud noise 

and the reduction of current consumption. In this case, the protection 

system inside the compressor activated turning off the unit. To solve 

the problem, disconnect and swap the wires between two of the 

phases, then connect the three-phases again.

-   That the voltage value lies within the pre-fixed limits and that 

unbalance between the three phases (three-phase power supply) is 

not above 3%.

-  If having to take measurements and perform checks that require the 

machine to run, you must:  

-  make sure that any remote control systems are disconnected; however, 

keep in mind that the PLC on the machine controls its functions and 

can enable and disable the components creating hazardous situations 

(e.g. power and rotate the fans and their mechanical drive systems). 

-  Operate with the electrical board open the shortest time possible

-  Close the electrical board as soon as the single measurement or 

control is performed  

ATTENTION

The anti-freeze set temperature can only be varied by an authorised 

after-sales centre and only after having checked that there is a suitable 

% of anti-freeze solution in the water circuit.

Whenever this alarm intervenes, call the nearest authorised after-sales 

service immediately

- Control of the water flow rate alarm, the unit provides for the 

management of a flow rate alarm controlled by a differential pressure 

switch or flow switch if provided. This type of safety device intervenes 

after the first 30 seconds of pump functioning, if the water flow rate is 

not sufficient. The intervention stops the compressor and the pump 

itself.

Содержание WWM 0500

Страница 1: ...TRANSLATION FROM ORIGINAL 60Hz 20 10 5046100_08 DUAL CIRCUIT COMPACT MODULE RELIABLE AND MODULAR MAX 2 LEVELS OF STACKABLE UNITS EASY AND QUICK TO INSTALL UP TO 36 CONNECTABLE UNITS See the modularity options WWM HEAT PUMP WITH REVERSIBLE WATER SIDE ...

Страница 2: ......

Страница 3: ...hest grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modifications considered necessary for the improvement of the product at any time and without the obligation for any notice thereof Thank you once again AERMEC S p A ...

Страница 4: ...4 ...

Страница 5: ...LIC CONNECTIONS 13 COOLING HYDRAULIC CIRCUIT 14 ELECTRICAL CONNECTIONS 17 ELECTRICAL POWER CONNECTION TO THE POWER SUPPLY MAINS 17 WWM ELECTRICAL DATA CONNECTED IN SERIES 18 UNITS CONNECTION 19 ELECTRICAL CONNECTION WITH BUS BAR 22 ELECTRICAL CONNECTION WITH CABLES 22 MODULARITY OPTIONS 24 COMMISSIONING WARNINGS 26 MAINTENANCE 27 EXTRAORDINAIRE MAINTENANCE 30 MAINTENANCE LIST OF THE RECOMMENDED PE...

Страница 6: ...necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate ventilation and provide refrigerant detectors when necessary The machine must not be installed in environments with risk of explosion but in a suitable place In particular if intended for indoor use it cannot be installed outdoors ...

Страница 7: ...xtures with ethylene glycol propylene in a maximum concentration of 30 The machine must only be employed for the use for which it was made any other use can be dangerous and void the warranty prEVEntions Make sure that the protections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate p...

Страница 8: ...tification data of the product and by the technical plate bearing the technical data of your unit If the product is damaged send a registered letter with the details of the problem to the shipping company within 48 working hours from delivery lifting The units are delivered on a pallet Should you desire to lift using the forklift or pallett jack we recommend opening the forks as much as possible t...

Страница 9: ...ndbreaks if the wind speed exceeds 2 2 m s The soil under the unit must be flat smooth and sufficiently strong to withstand the weight of the unit with a full refrigerant load as well as the occasional presence of the normal maintenance equipment In locations exposed to frost if the unit is installed on soil the support base must rest on concrete columns with a depth greater than the normal depth of...

Страница 10: ...25 3 24 7 25 9 Chiller bus bar headers kit 1 078 2 376 671 26 4 561 22 1 25 4 24 2 25 8 24 6 Chiller without bus bars headers kit 1 042 2 296 671 26 4 564 22 2 25 3 24 3 25 7 24 7 1 2 YG XG 3 4 TOP VIEW A A1 C C1 C2 B B1 B2 MINIMUMTECHNICAL SPACES WWM A1 B1 B2 C1 C2 0500 mm 500 1000 1000 1000 1000 in 19 7 39 4 39 4 39 4 39 4 DIMENSIONS WWM 0500 Vers 0500 A in H A 51 2 B in H A 52 4 C in H A 45 3 E...

Страница 11: ...11 EXAMPLE OF INSTALLATION Example of a stack in line installation It is recommended to fasten the units to an inertial structure that is installed on vibration dampers as shown in the image ...

Страница 12: ... behind the unit in order to make the header piping connections between modules If space cannot be made behind the unit adjacent piping headers must be connected prior to connecting the chiller chassis to front of the piping header Before removing the manifolds also remove the grooved heat exchanger connection joints ...

Страница 13: ...gs After performing a leak test insulate the pipes to reduce heat loss and prevent the formation of condensation If the external water pipes are in an area where it is likely that the environment temperature drops below 0 C insulate the pipes and provide an electric heater As an option you can also protect the pipes inside the unit Check the continuity of the earthing ATTENTION You must install th...

Страница 14: ...ED HYDRAULIC CIRCUIT MANUAL 10 STEPS 2 WAY VALVE MODULATING 2 WAY VALVE WATER OUTLET WATER INLET CONDENSER EVAPORATOR ON OFF 2 WAY VALVE WATER INLET PD ONLY FOR PN10 145 psi CIRCUIT TD ONLY FOR PN21 300 psi CIRCUIT WATER OUTLET MANUAL 10 STEPS 2 WAY VALVE MINIMUM WATER CONTENT WWM 0500 Minimum recomended water content l kW gal Ton 4 3 72 Minimum recomended water content l kW gal Ton 8 7 43 Minimum...

Страница 15: ...liquido Liquidtemp probe SLQ Sonda temp uscita acqua Wateroutlettemp probe SUW sonda di temp uscita acqua cond cond wateroutlettemp probe SUWH trasduttore di alta pressione highpressuretransducer TAP trasduttore di bassa pressione lowpressuretransducer TBP trasmettitore differenziale differentialpressuretransmitter TD Valvola 2 vie 2way valve V2V 0 80x valvola di sicurezza safety valve VSIC 0 86x ...

Страница 16: ...in Ø GROOVED JOINTS 6 KEY Evaporator Condenser HYDRAULIC COMPONENTS NOT SUPPLIED BUT MANDATORY Safety valve by the installer assembly valves adjusted to the static pressure of the unit 10bar 21bar Water filter on the inlet evaporator and condenser eventually Aermec s accessory KITIDRO_WWM ...

Страница 17: ...r these parameters are not respected contact the electric energy public body For electric connections use the cables with double isolation according to the Standards in force on this subject in the different countries it is mandatory The use of an omnipolar magnet circuit breaker switch in compliance with the current Standards contact opening at least 0 12 in with suitable cut off power and differ...

Страница 18: ...6 1126 683 739 700 7 1269 795 850 800 8 1411 906 962 800 9 1554 1018 1074 1000 ALIM 230 3 60 Q tyWWM LRA A MCA A MOP A Recom fuse A 1 212 61 87 80 2 276 114 141 125 3 340 168 195 175 4 405 222 249 225 5 469 276 303 300 6 533 330 356 350 7 597 384 410 400 8 662 438 464 450 9 726 492 518 500 ALIM 460 3 60 Q tyWWM LRA A MCA A MOP A Recom fuse A 1 156 54 78 75 2 204 103 127 125 3 251 152 175 175 4 298...

Страница 19: ... inside the power supply box there are bus bars or a terminal for the connection After removing the top panel disassembly the side panels on both sides ALWAYS link the units from left to right 1 First connect the hydraulic system with the dedicated grooved joints 2 Connect the electrical system 3 Connect the units together with M10 screws not supplied ATTENTION REMEMBER THAT THE SIDE PANELS LEFT A...

Страница 20: ...be removed Power supply 208 230V Supplied as standard 2 bus bars for each phase The use of one or more bars depends on the total current of the line therefore on how many WWM are connected together Power supply 460 575V Supplied as standard 1 bus bar for each phase In case of electrical connection with Bus Bars it is suggested to evaluate the installation of the KREC_WWM accessory Accessory KREC_W...

Страница 21: ...upplied For 2 level configuration fix the units in a linear way first and then one above the other Fix the base of the top unit in the cover of the bottom one In case of 2 level configuration follow the assembly sequence for a correct installation of the unit 1 2 3 4 5 6 7 8 ...

Страница 22: ...22 ELECTRICAL CONNECTION WITH BUS BAR TOP VIEW ELECTRICAL CONNECTION WITH CABLES TOP VIEW TOP VIEW FRONT VIEW SIDE VIEW use these clamps for cable connection ...

Страница 23: ...this way it s possible to access the top part of the cooling circuit Front opening to access the bars Nuts to be controlled periodically for a correct screw tightening Open the front panel of the bus bar box for inspection maintenance ...

Страница 24: ...ooling capacity ton 245 7 DIMENSIONS mm in A 2 600 102 4 B 6 650 262 0 C 1 150 45 3 FEATURES WWM units n x9 Multichiller_EVO n x1 Cooling capacity ton 245 7 DIMENSIONS mm in A 2 600 102 4 B 3 990 157 2 C 1 850 72 9 FEATURES WWM units n x9 Multichiller_EVO n x1 Cooling capacity ton 245 7 DIMENSIONS mm in A 1300 51 2 B 6650 262 0 C 1850 72 9 FEATURES WWM units n x18 Multichiller_EVO n x2 Cooling cap...

Страница 25: ...ING CIRCUIT HYDRONIC CIRCUIT FEATURES WWM units n x9 Multichiller_EVO n x1 Cooling capacity ton 245 7 mm in A 2 600 102 4 B 3 990 157 2 C 2 300 90 6 FEATURES WWM units n x36 Multichiller_EVO n x4 Cooling capacity ton 982 7 mm in A 2 600 102 4 B 11 970 471 6 C 2 300 90 6 FEATURES WWM units n x18 Multichiller_EVO n x2 Cooling capacity ton 491 3 mm in A 2 600 102 4 B 6 650 262 0 C 2 300 90 6 ...

Страница 26: ...ow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel must show the block Finally re open the valve and rearm the block COMMISSIONING Once all the aforementioned checks have been carried out the unit can be commissioned Close the door of the electrical panel Set the unit main switch to ON the unit will start after a few minutes OPERATIONS TO BE...

Страница 27: ...event their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position Place a sign reading Do not turn on maintenance in progress on the open isolator Equip yourself with the appropriate personal protective equipment helmet insulated gloves protective goggles accident prevention sh...

Страница 28: ...eplaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropriate equipment extractor antistatic bracelet etc when replacing electronic boards If replacing a motor compressor evaporator condensing coil or any other heavy element make sure that the lifting devices are c...

Страница 29: ...ar the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn off the machine remove the instruments and close the cooling circuit compartment The thermostatic valve must be calibrated with the machine off The high low pressure switch where present must be tested with the ...

Страница 30: ...base Disconnect the electrical box Close all taps valves of the hydraulic circuit Unscrew the screws that keep the cooling circuit in the unit There s the possibility to remove the group with the transpallet RECOMMENTED Drain the water from the exchanger with the drain taps Disconnect the water pipes of the exchangers by removing the grooved joints Remove the cover of the main switch and the lower...

Страница 31: ...rticular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simultaneous presence of air and water reduces yield and can benefit the arising of rust INTERVENTIONSTO COOLING CIRCUIT Functioning at full load Overheating temperature measurement Subcooling temperature...

Страница 32: ...nctioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMMISSIONING AND DISPOSAL OF THE MACHINE COMPONENTS ATTENTION The unit contains greenhouse effect fluoride gases covered by the Kyoto Protocol The law prohibits its dispersion in the environment and requires its r...

Страница 33: ...alth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased Please contact your local authority for further details Illegal dumping of the product by the user entails the application of administrative sanctions provided by law ...

Страница 34: ......

Страница 35: ......

Страница 36: ...EC S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data ...

Отзывы: