HYDRAULIC CIRCUIT
WWM _refrigerant circuit
Condenser
Evaporator
WWM _hydraulic circuit
Evaporator
Condenser
ON/OFF 2 WAY VALVE
MANUAL 10 STEPS 2 WAY VALVE
MANUAL 10 STEPS 2 WAY VALVE
MODULATING 2 WAY VALVE
Water inlet
Water outlet
Water inlet
Water outlet
CONDENSER
EVAPORATOR
ONLY PN10 (145 psi)
RATED HYDRAULIC
CIRCUIT
ONLY PN10 (145 psi)
RATED HYDRAULIC
CIRCUIT
MANUAL 10 STEPS 2 WAY VALVE
MODULATING 2 WAY VALVE
WATER OUTLET
WATER INLET
CONDENSER
EVAPORATOR
ON/OFF 2 WAY VALVE
WATER INLET
PD ONLY FOR PN10 (145 psi) CIRCUIT
TD ONLY FOR PN21 (300 psi) CIRCUIT
WATER OUTLET
MANUAL 10 STEPS 2 WAY VALVE
MINIMUM WATER CONTENT
WWM 0500
Minimum recomended water content
l/kW - gal/Ton
4/3.72
Minimum recomended water content
(
*
)
l/kW - gal/Ton
8/7.43
(*)Minimum water content for process applications or operating at low external
temperatures and low load.
Control on water inlet temperature.
Design Δt less than 5°C.