AERMEC WRK0300H Скачать руководство пользователя страница 30

30

INDICATIVE LAYOUT MODEL WRK 700

Power lines input

L1-L2-L3

Earthing

PE

auxiliary terminal 

board position

COMMISSIONING - WARNINGS

Please note that, on request by the Aermec customer or the legitimate 

owner of the machine, the units in this series can be started up by 

the AERMEC After-Sales Service in your area

 (valid only on ITALIAN 

territory). 

The start of operation must be scheduled in advance based 

on the time frame for the completion of works for the system. Prior to the 

intervention, all other works (electrical and hydraulic hook-ups, priming 

and bleeding of air from the system) must have been completed.

START-UP

OPERATIONS TO BE PERFORMED WITH NO VOLTAGE PRESENT

 ATTENTION 

the unit is not working:

Check:

-  All safety conditions have been respected

-  The unit is correctly fixed to the support surface

-  The minimum technical spaces have been respected 

-  That the main power supply cables have appropriate cross-section, 

which can support the total consumption of the unit. (see electric 

data sections) and that the unit has been duly connected to the 

ground.

-  That all the electrical connections have been made correctly and all 

the terminals adequately tightened.

-   Check for refrigerant gas leaks, especially near the pressure points 

of pressure gauges, pressure transducers and pressure switches. 

(vibrations during transport may have loosened the connections).

OPERATIONS TO BE PERFORMED WITH THE UNIT LIVE

 

ATTENTION 

the unit is still not working:

-  Supply power to the unit by turning the master switch to the ON 

position.

-  Use a tester to verify that the value of the power supply voltage to 

the phases is equal to 400V ± 10%; also verify that the unbalance 

between phases is no greater than 3%.

-  Check that the connections made by the installer are in compliance 

with the documentation.

-  Verify that the resistor of the compressor sump is working by 

measuring the increase in temperature of the oil pan. The resistance/s 

must function for at least 12 hours before start-up of the compressor 

and in any event, the temperature of the oil pan must be 10-15°C 

higher than room temperature.

HYDRAULIC CIRCUIT CONTROLS

-  Check that all hydraulic connections are made correctly, that the 

plate indications are complied with and that a mechanical filter has 

been installed in each inlet heat exchanger. 

(Mandatory component 

for warranty to be valid).

-  Make sure that the circulation pump/s is operating and that the 

water flow rate is sufficient to close the contact of the flow switch, if 

installed.

-  Check the water flow rate, measuring the pressure difference 

between inlet and outlet of the evaporator and calculate the flow rate 

using the evaporator pressure drop tables present in this manual.

-  Check the correct functioning of the flow meters if installed. Closing 

the cut-off valve at the output of the heat exchanger; the unit control 

panel must show the block. Finally re-open the valve and rearm the 

block

COMMISSIONING

-  Once all the aforementioned checks have been carried out, the unit 

can be commissioned

-  Close the door of the electrical panel.

-  Set the unit main switch to ON, the unit will start after a few minutes

OPERATIONS TO BE PERFORMED WITH MACHINE ON

 ATTENTION 

the unit is working:

Check:

-   That the compressor input current is lower than the maximum 

indicated in the electrical data table.

-   Before starting the unit, check that the compressor rotates in the 

correct direction through a three-phase protection. The spiral 

compressors compress in one direction of rotation only. Therefore, 

it is essential for the phase of the three-phase spiral compressors 

to be correctly connected (the correct direction of rotation can be 

controlled when the pressure on the intake side decreases and that 

on the flow side increases with the compressor in operation). If the 

connection is incorrect, the direction of rotation is reversed: this 

causes a loud noise and the reduction of current consumption. In this 

case, the protection system inside the compressor activated turning 

off the unit. To solve the problem, disconnect and swap the wires 

between two of the phases, then connect the three-phases again.

-   That the voltage value lies within the pre-fixed limits and that 

unbalance between the three phases (three-phase power supply) is 

not above 3%.

If having to take measurements and perform checks that require the 

machine to run, you must:  

-  make sure that any remote control systems are disconnected; 

however, keep in mind that the PLC on the machine controls its 

functions and can enable and disable the components creating 

hazardous situations (e.g. power and rotate the fans and their 

mechanical drive systems). 

-  Operate with the electrical board open the shortest time possible

-  Close the electrical board as soon as the single measurement or 

control is performed  

ATTENTION

The anti-freeze set temperature can only be varied by an authorised 

after-sales centre and only after having checked that there is a suitable 

% of anti-freeze solution in the water circuit.

Whenever this alarm intervenes, call the nearest authorised after-sales 

service immediately

- Control of the water flow rate alarm, the unit provides for the 

management of a flow rate alarm controlled by a differential pressure 

switch or flow switch if provided. This type of safety device intervenes 

after the first 30 seconds of pump functioning, if the water flow rate is 

not sufficient. The intervention stops the compressor and the pump 

itself.

Содержание WRK0300H

Страница 1: ... o m o r i g i n a l I n s t a l l a t i o n m a n u a l EN W R K 60Hz 2 1 1 2 5 8 9 0 7 3 5 _ 0 1 REVERSIBLE WATER COOLED HEAT PUMP GAS SIDE C o o l i n g c a p a c i t y 1 9 2 4 9 3 t o n H e a t i n g c a p a c i t y 2 8 1 7 8 1 7 4 2 0 2 5 B T U h ...

Страница 2: ......

Страница 3: ...EC products are synonymous with Safety Quality and Reliability The data may undergo modifications considered necessary for the improvement of the product at any time and without the obligation for any notice thereof Thank you once again AERMEC S p A This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environm...

Страница 4: ...TERISTICS 16 TECHNICAL DRAWINGS HYDRAULIC CONNECTIONS 21 ELECTRICAL CONNECTIONS 25 ELECTRICAL DATA 26 PUMPS ELECTRICAL DATA 26 OPERATING RANGE 27 ELECTRIC POWER CONNECTION TO THE ELECTRICAL MAINS 29 INDICATIVE LAYOUT MODEL WRK 700 30 COMMISSIONING WARNINGS 31 MAINTENANCE 32 MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS 35 CONFIGURATOR 37 ACCESSORIES 37 COMPATIBILITY OF ACCESSORIES 38 ...

Страница 5: ...5 CERTIFICATIONS COMPANY CERTIFICATIONS SAFETY CERTIFICATIONS ...

Страница 6: ... The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate ventilation and provide refrigerant detectors when necessary The machine must not be installed in environments with risk of explosion but in a suitable place In particular if intended for indoor use it cannot be installed outdoors The machines must...

Страница 7: ...xtures with ethylene glycol propylene in a maximum concentration of 30 The machine must only be employed for the use for which it was made any other use can be dangerous and void the warranty PREVENTIONS Make sure that the protections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate p...

Страница 8: ... unità deve essere eseguita da personale qualificato Seguire scrupolosamente le istruzioni di sollevamento indicate con delle etichette poste sull unità Le operazioni di sollevamento dell unità devono essere eseguite con estrema attenzione per evitare urti su telaio pannelli quadro elettrico ecc NOTA Le unità possono essere protette dai danni durante il trasporto tramite elementi di plastica La ma...

Страница 9: ...s exposed to frost if the unit is installed on soil the support base must rest on concrete columns with a depth greater than the normal depth of frost of the soil It is always advisable to build a support base separate from the main building to avoid the transmission of vibrations Stationary appliance for normal applications the rigidity of the unit and the positioning of point loads allow for an ...

Страница 10: ... L in 31 5 31 5 31 5 31 5 31 5 31 5 31 5 31 5 WITHOUT HYDRONIC KIT WRK A1 in 39 4 B1 in 39 4 B2 in 39 4 C1 in 39 4 C2 in 39 4 MINIMUM TECHNICAL SPACES WRK vers 0300 0330 0350 0500 0550 0600 0650 0700 A L in 66 0 66 0 66 0 74 3 74 3 74 3 74 3 74 3 B L in 74 5 74 5 74 5 121 7 121 7 121 7 121 7 121 7 C L in 31 5 31 5 31 5 31 5 31 5 31 5 31 5 31 5 WITH HYDRONIC KIT A1 A C B B1 B2 C1 C2 ...

Страница 11: ...23 7 46 9 11 9 WRK0500H 700HWITH HYDRONIC KIT 27 3 73 4 15 6 MODEL E F G in in in WRK0300H 350HWITHOUT HYDRONIC KIT 11 9 25 9 12 0 WRK0300H 350HWITH HYDRONIC KIT 11 9 46 9 11 9 ANTIVIBRANTS POSITION TOP VIEW TOP VIEW 28 8 in 1 4 in 1 4 in 28 8 in 1 4 in 1 4 in ...

Страница 12: ...12 Xg Yg Xg Yg CENTER OF GRAVITY POSITION TOP VIEW MODELS 0500 0700 TOP VIEW MODELS 0300 0350 ...

Страница 13: ...33 26 23 18 U W 2 546 42 5 15 2 34 26 23 18 V Z 2 701 40 3 14 2 37 25 23 16 M O U W 2 668 43 8 15 0 33 25 24 18 N P V Z 2 976 43 1 14 3 35 24 25 17 WRK0550H L 2 238 26 5 12 8 40 23 24 14 M O 2 657 43 5 15 3 33 25 24 18 N P 2 811 45 0 15 6 32 25 24 19 U W 2 734 44 5 15 3 32 25 24 19 V Z 2 888 42 3 14 3 35 24 24 16 M O U W 2 855 45 6 15 1 32 24 25 19 N P V Z 3 164 44 8 14 4 34 23 25 18 WRK0600H L 2 ...

Страница 14: ... 18 AVX313 M O U W 2 723 44 9 15 0 30 27 23 21 AVX343 N P V Z 3 053 43 9 14 3 32 26 23 19 AVX343 WRK0550H L 2 227 27 1 12 8 37 25 23 16 AVX342 M O 2 712 44 5 15 3 29 28 22 21 AVX343 N P 2 877 46 1 15 6 28 28 22 22 AVX343 U W 2 789 45 5 15 3 29 27 22 21 AVX343 V Z 2 954 42 7 14 2 32 27 23 19 AVX343 M O U W 2 921 46 6 15 1 29 26 23 21 AVX343 N P V Z 3 252 45 4 14 4 31 26 24 20 AVX343 WRK0600H L 2 30...

Страница 15: ...ttings Install stop valve near the water inlet and outlet fittings After performing a leak test insulate the pipes to reduce heat loss and prevent the formation of condensation If the external water pipes are in an area where it is likely that the environment temperature drops below 32 F insulate the pipes and provide an electric heater As an option you can also protect the pipes inside the unit C...

Страница 16: ...ANDATORY 11 Drain valve 12 Storage tank 13 Antifreeze electric heater 14 Drain valve 15 Pressure gauge 12 14 1 2 2 4 4 5 5 5 7 11 11 11 10 6 6 8 8 3 3 1 2 2 4 4 5 5 7 11 11 10 8 13 15 15 9 9 CONDENSER EVAPORATOR Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese ...

Страница 17: ...ge tank 18 Antifreeze electric heater 19 Drain valve 20 Pressure gauge 17 19 6 6 1 2 2 10 10 11 11 11 13 5 16 16 4 12 7 14 9 3 3 1 2 2 10 10 11 11 13 5 16 4 14 18 20 20 15 15 7 7 8 8 M O N P CONDENSER EVAPORATOR O P Options not available for sizes 0650 0700 Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Temperature 65 C Oxygen content 0 1 ppm Max ...

Страница 18: ...freeze electric heater 17 Drain valve 18 Pressure gauge 19 Pump 15 17 8 1 2 2 9 9 10 10 10 11 7 14 14 6 4 19 12 12 3 3 1 2 2 9 9 10 10 11 7 14 6 12 16 18 18 13 13 U W 4 4 5 5 V Z CONDENSER EVAPORATOR W Z Options not available for sizes 0650 0700 Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Temperature 65 C Oxygen content 0 1 ppm Max glycol amoun...

Страница 19: ...17 Antifreeze electric heater 18 Drain valve 19 Pressure gauge 16 18 8 8 1 2 2 10 10 11 11 11 12 7 15 15 6 4 4 13 9 3 3 1 2 2 10 10 11 11 12 7 15 6 13 17 19 19 14 14 4 4 5 5 M O N P U W 4 4 5 5 V Z CONDENSER EVAPORATOR O P W Z Options not available for sizes 0650 0700 Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Temperature 65 C Oxygen content 0...

Страница 20: ...tifreeze electric heater 14 Drain valve 15 Pressure gauge 12 14 14 1 2 2 4 4 5 5 5 7 7 11 11 11 10 6 6 8 8 8 3 4 3 3 1 2 2 4 4 5 5 7 11 11 11 10 8 13 15 15 9 1 2 2 4 5 5 5 6 9 9 DESUPERHEATER CONDENSER EVAPORATOR Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese...

Страница 21: ...let Evaporator Inlet EVA Inlet evaporator Outlet CND Outlet condenser Inlet CND Inlet condenser 28 5 in 31 5 in 0 7 in 12 0 in 25 9 in 11 9 in 66 0 in 49 8 in 15 4 in 58 9 in 43 5 in 43 5 in 15 4 in 8 9 in Outlet EVA 2 1 2 Inlet EVA 2 1 2 Inlet CND 2 1 2 Outlet CND 2 1 2 13 9 in 8 9 in 31 5 in ...

Страница 22: ...700 WITHOUT HYDRONIC KIT 0 7 in 11 9 in 46 9 in 82 5 in 2 4 in 84 9 in 23 7 in 74 3 in 8 9 in 8 9 in 13 8 in 15 4 in 43 5 in 43 5 in 15 4 in 31 5 in Outlet EVA 2 1 2 Inlet EVA 2 1 2 Inlet CND 2 1 2 Outlet CND 2 1 2 ...

Страница 23: ...T SYSTEM SIDE GEOTHERMIC SIDE 0 7 in 11 9 in 11 9 in 46 9 in 28 5 in 31 5 in 66 0 in 3 7 in 70 7 in 74 5 in 9 3 in 58 9 in 32 3 in 50 6 in 15 2 in 31 5 in 9 3 in 8 9 in Outlet EVA 2 1 2 Inlet EVA 2 1 2 Inlet CND 2 1 2 Outlet CND 2 1 2 ...

Страница 24: ...KIT SYSTEM SIDE GEOTHERMIC SIDE 0 7 in 15 6 in 73 4 in 27 3 in 74 3 in 3 2 in 2 4 in 116 2 in 121 7 in 15 4 in 16 2 in 58 9 0 8 in 10 2 0 8 in 32 3 0 8 in 53 4 0 8 in Outlet EVA 2 1 2 Outlet CND 2 1 2 Inlet EVA 2 1 2 Inlet CND 2 1 2 ...

Страница 25: ...e manufacturer cannot be considered responsible for any damage caused by the lack of or ineffective appliance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the necessary qualifications by law suitably trained and informed on the risks related to these operat...

Страница 26: ...SCE 40 125 55 Lowara NSCE 40 125 55 Pn kW 2 2 2 9 2 9 4 0 4 0 4 0 5 5 5 5 FLA A 4 0 5 5 5 5 6 7 6 7 6 7 8 9 8 9 ELECTRICAL DATA Option not available Version Integrated hydronic kit user side Integrated hydronic kit source side 0300 0330 0350 0500 0550 0600 0650 0700 Peak current LRA L A 148 178 213 214 223 190 230 278 L U V A 150 182 217 218 228 195 236 285 L M N A 150 182 217 218 228 195 236 285 ...

Страница 27: ... 3 7 3 7 3 7 3 Maximun water operating pressure PN psi 116 0 116 0 116 0 145 0 145 0 145 0 145 0 145 0 Cooling System side water in out 54 00 F 44 01 F Source side water in out 84 99 F 94 30 F Heating System side water in out 104 F 113 F Source side water in out 50 00 F 44 60 F OPERATING RANGE The units in standard configuration are not suitable for installation in salty environment The values ind...

Страница 28: ...0 0 60 0 68 0 80 0 100 0 122 0 140 0 149 0 149 0 95 0 68 0 160 0 F 10 0 14 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 F B A 1 T condenser 46 4 F Key A Water produced system side F B Processed water temperature source side F 1 T condenser 46 4 F 0 0 20 0 40 0 60 0 68 0 95 0 154 4 80 0 100 0 122 0 140 0 154 4 180 0 F 10 0 14 0 20 0 30 0 40 0 50 0 60 0 68 0 80 0 F B A 1 ...

Страница 29: ...nsulated copper piping and with the compressor Identify the clamps for the electric connection and always refer exclusively to the wiring diagram supplied with the unit Remove any protections from the cable fixing points For the functional connection of the unit take the power supply cable to the electric control board inside the unit and connect it to clamps L1 L2 L3 N if present and PE respectin...

Страница 30: ...30 INDICATIVE LAYOUT MODEL WRK 700 Power lines input L1 L2 L3 Earthing PE auxiliary terminal board position ...

Страница 31: ...ssure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel must show the block Finally re open the valve and rearm the block COMMISSIONING Once all the aforementioned checks have been carried out the unit can be commissioned Close the door of the electrical panel Set the ...

Страница 32: ...evention shoes etc Equip yourself with tools in good condition and make sure to have fully understood the instructions before using them For outdoor units do not perform interventions in dangerous weather conditions such as rain snow fog etc The cooling circuit contains under pressure refrigerant gas any operation must be performed by competent personnel in possession of the authorisations and qua...

Страница 33: ...essor evaporator condensing coil or any other heavy element make sure that the lifting devices are compatible with the weight to be handled In air units with independent compressor compartment do not access the fan compartment without having first disconnected the machine through the isolator on the board and having placed a sign reading Do not turn on maintenance in progress Always and only use o...

Страница 34: ...ressor inlet and outlet pipes Avoid using metratast that require the operator to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn off the machine remove the instruments and close the cooling circuit compartment The thermostatic valve must be calibrated with ...

Страница 35: ...nefit the arising of rust INTERVENTIONSTO COOLING CIRCUIT Functioning at full load Overheating temperature measurement Subcooling temperature measurement Exhaust gas temperature measurement Fans absorption measurement Compressors absorption measurement COMPRESSOR CHECKS Check oil level Check oil acidity Check the proper functioning of the casing resistance Check oil level sensor if any CHECKS ON H...

Страница 36: ...CUIT PARTS Check the proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves DECOMMISSIONING AND DISPOSAL OF THE MACHINE COMPONENTS ATTENTION The unit contains greenhouse effect fluoride gases covered by the Kyoto Protocol The law prohibits its dispersion in the environment and requires its recovery and delivery to the de...

Страница 37: ...nstant flow rate to the evaporators AVX Spring anti vibration supports VT Antivibration supports FACTORY FITTED ACCESSORIES T6 Double safety valve high and low pressure with exchange valve 1 2 3 Name WRK 4 5 6 7 Size 0300 0330 0350 0500 0550 0600 0650 0700 8 Operating field Standard mechanic thermostatic valve 9 Model H Heat pump reversible gas side 10 Version L Silenced 11 Evaporator Standard 12 ...

Страница 38: ... AVX343 L N AVX343 AVX343 AVX343 AVX343 AVX343 L V AVX313 AVX343 AVX343 AVX343 AVX343 L M AVX313 AVX343 AVX343 AVX343 AVX343 L M W AVX343 AVX343 AVX343 L N Z AVX343 AVX343 AVX343 L O U W AVX343 AVX343 AVX343 L P V Z AVX343 AVX343 AVX343 L Z AVX313 AVX343 AVX343 L O AVX313 AVX343 AVX343 L M V Z AVX343 AVX343 AVX343 AVX344 AVX344 L N U V W AVX343 AVX343 AVX343 AVX344 AVX344 L O V Z AVX343 AVX343 AVX...

Страница 39: ......

Страница 40: ...0 B e v i l a c q u a V R I t a l y T e l 3 9 0 4 4 2 6 3 3 1 1 1 F a x 3 9 0 4 4 2 9 3 5 7 7 m a r k e t i n g a e r m e c c o m w w w a e r m e c c o m 2 1 1 2 5 8 9 0 7 3 5 _ 0 1 DOWNLOAD THE LATEST VERSION http www aermec com qrcode asp q 17719 ...

Отзывы: