![AERMEC WRK0300H Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/aermec/wrk0300h/wrk0300h_installation-manual_2862073019.webp)
19
WITH USER AND SOURCE SIDE PUMPS
Components as standard
1
Plate heat exchanger
2
Water temperature sensors (IN/OUT)
3
Water filter
4
Pump
5
One-way valve
6
Flow switch
7
Drain valve
8
Drain valve
9
Expansion vessel
Components not provided and responsibility of
the installer
10 Anti-vibration joints
11 Flow shut-off valves
12 Pressure relief valve
13 Expansion vessel
14 Loading unit
15 Drain valve
16 Storage tank
17 Antifreeze electric heater
18 Drain valve
19 Pressure gauge
16
18
8
8
1
2
2
10
10
11
11
11
12
7
15
15
6
4
4
13
9
3
3
1
2
2
10
10
11
11
12
7
15
6
13
17
19
19
14
14
4
4
5
5
M-O
N-P
U-W
4
4
5
5
V-Z
CONDENSER
EV
APOR
AT
OR
O-P-W-Z:
Options not available for sizes 0650-0700
Water characteristics
System: Chiller with plate heat exchanger
PH
7,5 - 9
Total hardness
4,5 - 8,5 °dH
Temperature
< 65 °C
Oxygen content
< 0,1 ppm
Max. glycol amount
50 %
Phosphates (PO₄)
< 2ppm
Manganese (Mn)
< 0,05 ppm
Iron (Fe)
< 0,3 ppm
Alkalinity (HCO₃)
70 - 300 ppm
Chloride ions (Cl-)
< 50 ppm
Sulphate ions (SO₄)
< 50 ppm
Sulphide ion (S)
None
Ammonium ions (NH₄)
None
Silica (SiO₂)
< 30 ppm
Содержание WRK0300H
Страница 2: ......
Страница 5: ...5 CERTIFICATIONS COMPANY CERTIFICATIONS SAFETY CERTIFICATIONS ...
Страница 12: ...12 Xg Yg Xg Yg CENTER OF GRAVITY POSITION TOP VIEW MODELS 0500 0700 TOP VIEW MODELS 0300 0350 ...
Страница 30: ...30 INDICATIVE LAYOUT MODEL WRK 700 Power lines input L1 L2 L3 Earthing PE auxiliary terminal board position ...
Страница 39: ......