The fan coil tray has 2 condensate drains
on the right and left side. We recommend
using the condensate drain fitting on
the side of the hydraulic connections.
Install the drain condensate drain fitting
supplied. Seal the connection between
the tray and the fitting with silicone.
Seal the drain that is not used. Connect
the tray fitting to the condensate drain
network. Use a drain pipe, which must be
fixed to the tray fitting. The drain fittings
are designed only to be fixed to hoses
with suitable inner diameter. Avoid the
application of greater loads and do not
use them for other purposes. Make sure
that the drain not used is closed and does
not leak. The condensate drain network
must be properly sized and the pipelines
must be positioned in order to maintain
a suitable slope along the path (min.1%).
In the case of discharge to the sewer, it
is advisable to make a siphon which
prevents odours from returning into
the environment. Run an operating and
condensate drain system seal test by
pouring water in the tray.
48. CONDENSATE DRAIN
Should the coil rotate due to the hydraulic
connection, remove the front closing
panel and proceed as follows:
- Remove the condensate collection tray.
- Remove the cover from the coil by
loosening the screws.
- Remove the screws that fasten the coil
and remove the latter.
- Remove the push-out elements from the
right side.
– ATTENTION! Before rotating the coil, refer
to the coil rotation diagram.
The coil must be rotated and installed
correctly.
Rotate the coil correctly and fix it with the
previously remoVED_I screws. The spaces
between manifold and hole on the side
must be filled and sealed with insulation
material.
- Remount the cover on the coil by
fastening the screws.
- Close the holes left free from the
hydraulic connections on the left side
with insulation material.
- Remount the condensate collection tray.
The tray is set up for the condensate
drain on both sides. We recommend
using the condensate drain fitting placed
on the side of the hydraulic connections.
Make sure that the drain not used is closed
and does not leak.
- Remove the electrical connections from
the right side.
- Move the electrical connections to the
left side passing them through the cable
gland.
- Move the support plate, terminal board,
earthing jumper, and electrical devices
from the right to the left side.
- Remount the front closing panel.
49. COIL ROTATION