Aermec 13_01. 5641300_00
NRL 0280-0750 60Hz
EN
18. CONTROL AND SAFETY PARAMETERS
CALIBRATION
COOLING SET
Min
Max.
Default
Water inlet temperature in cooling mode
-10°C / 14°F
20°C / 68°F
7°C / 44,6°F
HEATING SET
Min
Max.
Default
Inlet water temperature in heating functioning mode
30°C / 86°F
55°C / 131°F
50°C / 122°F
ANTI FREEZE INTERVENTION
Min
Max.
Default
Intervention temperature of the anti-freeze alarm on the EV side (water outlet temperature)
-15°C / 5°F
4°C / 39,2°F
3°C / 37,4°F
TOTAL DIFFERENTIAL
Min
Max.
Default
Proportional temperature band within which the compressors are activated and deactivated
3°C / 5,4
10°C / 18
5°C / 10
Autostart
Auto
NRL 0280
NRL 0300
NRL 0330
NRL 0350
NRL 0500
NRL 0550
NRL 0600
NRL 0650
NRL 0700
NRL 0750
HIGH PRESSURE PRESSURE SWITCH MANUAL REARM
PA
psi / bar
580 / 40
580 / 40
580 / 40
580 / 40
580 / 40
580 / 40
580 / 40
580 / 40
580 / 40
580 / 40
HIGH PRESSURE TRANSDUCER
TAP
psi / bar
566 / 39
566 / 39
566 / 39
566 / 39
566 / 39
566 / 39
566 / 39
566 / 39
566 / 39
566 / 39
LOW PRESSURE TRANSDUCER
TBP
psi / bar
29 / 2
29 / 2
29 / 2
29 / 2
29 / 2
29 / 2
29 / 2
29 / 2
29 / 2
29 / 2
COOLING CIRCUIT SAFETY VALVES
AP
psi / bar
653 / 45
653 / 45
653 / 45
653 / 45
653 / 45
653 / 45
653 / 45
653 / 45
653 / 45
653 / 45
BP only heat pump version
psi / bar
435 / 30
435 / 30
435 / 30
435 / 30
435 / 30
435 / 30
435 / 30
435 / 30
435 / 30
435 / 30