29
Aermec 13_01. 5641300_00
NRL 0280-0750 60Hz
EN
KEY
(1)
Check that the highest user does not exce-
ed a level difference of 180.45ft / 55m.
(2) Check that the lowest user can sustain the
global pressure acting at that point.
H max (1) = 180.45ft / 55m
H = 40.19ft / 12.25m
H
H = 0 m
Pt
ar = H / 1
0
.2 + 0.3
Pt
ar = 1
.5 bar
Pt
ar = 1
.5 bar
H min (2)
ATTENTION
It is recommended to design systems with high
water content (minimum recommended values
shown in table), to limit:
1. 1. The hourly number of inversions between
functioning modes.
2. 2. Decrease in water temperature during
winter defrost cycles.
14. EXPANSION TANK CALIBRATION
The standard pressure value for pre-charging the ex-
pansion tank is 1.5 bar, and the volume is 25 litres/
6.6 gallon. Maximum value 6 bar.
The tank must be calibrated according to the
maximum difference in height (H) of the device (see
figure) according to the formula:
p (calibration) [bar] = H [m] / 10.2 + 0.3.
For example, if the level difference H is 20m, the
calibration value of the tank will be 2.3 bar.
If the calibration value obtained from the calculation
is lower than 1.5 bar (i.e. for H < 12.25), maintain
the standard calibration.
15. MINIMUM WATER CONTENT
Key:
NRL
n°
Compressor
(1) l/KW
(2) l/KW
0280
2
7
14
0300
0330
0350
0500
3
5
10
0550
0600
4
4
8
0650
0700
0750
(1)
Minimum water content
(2)
Minimum water content in the case of process
applications or applications with low outside
temperatures and low load.
Regolation on the temperature outlet water.
project
Δ
t less than 5°C/10°F.