12.  ELECTRICAL WIRINGS

The default NRL chillers are completely wired and 

only need the connection to the power supply net, 

downstream to a group switch, according to the to the 

regulations in force in the country where the machine 

is installed. 

It is also suggested to check:

• the mains supply characteristics, to ensure it is suita-

ble for the levels indicated in the electrical data table, 

also taking into consideration any other equipment 

that may be operating at the same time.

• The unit is only powered after the last (hydraulic and 

electric) installations.

• Follow the connections instructions of the phase 

conductors, and earth.

• The power line will have a special protection upstre-

am against short circuits and earth losses that sections 

the system according to other users.

• The voltage should be within a tolerance of ± 

10% of the rated supply voltage of the machine (for 

Three-phase units displacement max 3% between the 

phases). If these parameters are not respected, contact 

the energy supplier. For electrical wirings use isolated 

double cables according to the standards in force in the 

different countries.

• It is necessary to use a omnipolar thermomagne-

tic switch, in compliance with the CEI-EN standards 

(contact opening of at least 3 mm), with adequate 

switch capability and differential protection based on 

the followed electrical data table, installed as close as 

possible to the machine.

• It is necessary to carry out an efficient earth connec-

tion. The manufacturer can not be held responsible 

for any damage caused by the failure and ineffective 

earthing of the machine.

• For units with Three-phase power check the correct 

connection of the phases. 

WARNING

It is forbidden to use water pipes for the earthing of 

the machine.

12.1.  RECOMMENDED SECTION OF ELECTRIC 

CABLES

The cable sections indicated in the table are advised 

for a maximum length of 50 m.

For higher lengths or different types of cable installa

-

tion, it will be the DESIGNERS responsibility to carefully 

measure the line main switch, the supply power line 

and the earthing protection connection, and the wor-

king connection cables:

• the length

• the type of cable

• Absorption of the unit and its physical position, and 

room temperature.

WARNING:

Check that all power cables are  

correctly secured to the terminals when switched on 

for the first time and after 30 days of use. Afterwards, 

check the connection of the power cables every six 

months.Slack terminals could cause the cables and 

components to overheat.

ATTENTION

All electrical operations must be 

carried out by qualified personnel, 

in accordance with the corre-

sponding regulations, trained and 

informed about the risks related to 

such operations.

ATTENTION

The characteristics of electric lines 

and related components must be 

established by personnel authori-

sed to design electric installations, 

following international regulations 

and the national regulations of 

the country in which the unit is 

installed, in compliance with the 

legislative regulations in force at 

the moment of installation.

ATTENTION

For installation requirements, the 

wiring layout supplied with the 

unit must be compulsory referred 

to.  The wiring layout together 

with the manuals must be kept 

in good conditions and readily 

accessible for future operations on 

the unit.

ATTENTION

it is compulsory to check the 

machine sealing before connecting 

the electrical wiring. The machine 

should only be powered once the 

hydraulic and electric operations 

are completed.

NOTE

Field wiring by others which 

complies to the National 

Electrical Code & Local Codes.

*=DATA NOT AVAILABLE - CONTACT HOME

Содержание NRL 0280 FE

Страница 1: ...tenance Manual TRANSLATION FROM ORIGINAL 21 05 5641250_04 NRL FC 028 075 CHILLER HIGH EFFICENCY POWER SUPPLY 60Hz GAS FREE COOLING AHRI CERTIFICATION INTERTEK CERTIFICATION SCROLL COMPRESSOR AXIAL FAN...

Страница 2: ......

Страница 3: ...ence and in depth engineering research and it is built using top quality materials and advanced technologies In addition the CE mark guarantees that our appliances fully comply with the requirements o...

Страница 4: ...0 0650 0700 FA 12 7 4 NRL 0750 FA 12 8 Crate special wood cover for transport accessory 13 9 Hydraulic connection 14 9 1 Hydraulic connection NRL 0280 0350 FA 14 9 2 Hydraulic connection NRL 0500 0750...

Страница 5: ...coils at the desired temperature This is the most economical mode of the unit with only the fans operating in speed modulation MIXED FREE COOLING COMPRESSORS the compressors operate in integration wi...

Страница 6: ...yes Hydraulic circuit Version 01 04 0280 0300 0330 0350 0500 0550 0600 0650 0700 0750 Water filter yes yes yes yes yes yes yes yes yes yes Flow switch yes yes yes yes yes yes yes yes yes yes Safety va...

Страница 7: ...r SYSTEM SIDE EVAPORATION Production cold water 2 exchanger SOURCE SIDE CONDENSATION Heat exchange with the air 3 exchanger SYSTEM SIDE EVAPORATION FREE COOLING Production cold water H2 O RETURN SYSTE...

Страница 8: ...have thorough knowledge of the operations and any dangers that may arise at the moment in which the installation operations are carried out 4 SELECTION AND PLACE OF INSTALLATION 1100 mm 43 in 800 mm 3...

Страница 9: ...0 mm 43 in 2950 mm 116 in 3010 mm 119 in 1160 mm 46 in 1606 mm 63 in 1100 mm 43 in 2950 mm 116 in 1750 mm 69 in 3010 mm 119 in 1160 mm 46 in 6 2 NRL 0330 0350 FE 6 3 NRL 0500 0550 FA 3260 mm 128 in 11...

Страница 10: ...0650 0700 FA 6 5 NRL 0750 FA 1990 mm 78 in 4010 mm 158 in 4070 mm 160 in 1100 mm 43 in 1160 mm 46 in 1875 mm 74 in 1955 mm 77 in 1500 mm 59 in 4355 mm 172 in ATTENTION NRL 0750 FA ALWAYS USE ALL THE...

Страница 11: ...00 mm 8 in 200 mm 8 in 200 mm 8 in 1275 mm 50 in 1275 mm 50 in 1275 mm 50 in 1275 mm 50 in 200 mm 8 in 1400 mm 55 in 1462 mm 58 in 200 mm 8 in 200 mm 8 in 1400 mm 55 in 1462 mm 58 in 200 mm 8 in 7 1 N...

Страница 12: ...50 FA 200 mm 8 in 200 mm 8 in 2158 mm 85 in 1440 mm 57 in 200 mm 8 in 200 mm 8 in 2158 mm 85 in 1440 mm 57 in 100 mm 4 in 100 mm 4 in 100 mm 4 in 100 mm 4 in 1500 mm 59 in 1500 mm 59 in 1500 mm 59 in...

Страница 13: ...NRL MODELS CRATE 0280 FA FE 02 0300 FA FE 02 0330 FA FE 02 0350 FA FE 02 0500 FA FE 02 0550 FA FE 02 0600 FA FE 03 0650 FA FE 03 0700 FA FE 03 0750 FA FE 04 CRATE A in B in C in CRATE02 87 9 138 7 50...

Страница 14: ...750 FA WARNING Clean the system carefully before connecting the unit Cleaning will eliminate any residues suck as drops of solder waste rust or other impurities from the piping These substances could...

Страница 15: ...839 538 212 1616 636 30 29 21 20 VT 10 NRL0550F P4 2638 537 211 1620 638 30 29 21 20 VT 13 NRL0550F P3 2552 537 211 1579 622 31 29 20 19 VT 13 WEIGHT OF RUNNING UNITS NRL TYPE WEIGHT lib CENTER OF GRA...

Страница 16: ...0F 00 3196 550 217 1723 679 7 7 7 7 33 0 33 1 9 2 9 2 VT 22 NRL0650F 04 3703 476 187 1491 587 8 8 6 7 37 5 28 6 10 4 8 0 VT 22 NRL0650F 03 3593 490 193 1535 604 8 6 6 9 36 6 29 5 10 2 8 2 VT 22 NRL065...

Страница 17: ...g to the machine must be properly si zed to the actual flow of water re quired by the system in operation The water flow to the exchanger must always be constant ATTENTION Carefully wash the plant bef...

Страница 18: ...one ammonia ions none Silicone ions less than 30 ppm ATTENTION The choice and the installation of components external to the NRL up to the installer who must ope rate according to the rules of good te...

Страница 19: ...YSTEM Before starting to drain the system turn off the unit Check that the water system load restore tap is closed Open the drain tap outside the machine and all the vent valves of the system and the...

Страница 20: ...water pipes for the earthing of the machine 12 1 RECOMMENDED SECTION OF ELECTRIC CABLES The cable sections indicated in the table are advised for a maximum length of 50 m For higher lengths or differ...

Страница 21: ...AD PUMP P3 P4 03 04 I EC INVERTER FAN LRA FA 230V A 382 402 388 463 481 537 FE 242 290 304 374 MCA FA 230V 150 175 175 225 300 300 FE 90 90 110 150 MOP FA 230V 175 200 200 250 300 300 FE 110 110 125 1...

Страница 22: ...od Anti freeze alarm See User Manual Restart Manual Elec cal Heater OFF ON Temperature 5 C 4 C Circula ng Pump OFF ON Temperature 5 C 4 C Only for pure water not added with glycol WATER FLOW ALARM If...

Страница 23: ...lefonico KIT PGD1 ACCESSORIO S90CONN cavo di collegamento Cavo telefonico External Alarm J15 N08 C8 NC8 Circula ng Pump J12 N01 CP01 Remote Control PGD1 Circula ng Pump J22 N018 CP02 External Circuit...

Страница 24: ...s the list of active and historical alarms red LED on active alarm MENU ACTIVATION key Pressing this key activates the navigation between menus orange LED on winter operating mode active EXIT MENU key...

Страница 25: ...owmask English ESCtoconfirm 20 A Remaining time for software loading this value shows the remain ing time to starting the software loaded on the unit and passing the to system language selection B Sys...

Страница 26: ...nly modi ed by personnel quali ed in the installa on and con gura on of the unit Menu structure and naviga on Index Icon Menu Menu function A MAIN The screens in this menu display the current conditio...

Страница 27: ...e to move between the screens using the arrow keys the key to move to the previous parameter and the key to move to the next parameter c When the desired parameter is shown press the key to enter the...

Страница 28: ...cqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improving the product at any time with a...

Отзывы: