EXPANSION VESSEL SETTING
The expansion tank volume is 6.3 gal. The standard value of the expansion tank pre-charge pressure is 21.8 psi, but this can be calibrated up to a maximum of 87.0 psi.
The expansion tank pressure setting has to be adjusted based on the difference in height (H) of the installation (see figure) according to the formula: p (rating) [bar] = H [ft] /
33.5 + 1.0.
For example: if level difference H is equal to 65.6 ft, the calibration value of the vessel will be 33.4 psi.
If the calibration value obtained from the formula is less than 21.8 psi (i.e. for H < 40.2), use the standard calibration.
Key
A
Expansion vessel
1
Check that highest installation
is not higher than 180.4 ft.
2
Ensure that lowest utility can
withstand global pressure in
that position
H max (1) = 55 m
H = 0 m
H = 12.25 m
Ptar = H / 10.2 + 0.3
Ptar = 1.5 bar
Ptar = 1.5 bar
H min (2)