background image

2

  

These

 

instructions

 

are

 

intended

 

as

 

a

 

general

 

guide

 

only

 

and

 

do

 

not

 

supersede

 

any

 

national

 

or

 

local

 

codes

 

in

 

any

 

way.

 

The

 

installa

tion

 

must

 

comply

 

with

 

all

 

state,

 

and

 

local

 

codes

 

as

 

well

 

as

 

the

 

National

 

Electrical

 

Code.

 



The

 

heat

 

pump

 

is

 

designed

 

and

 

approved

 

for

 

outdoor

 

use

 

only.

 



The

 

heat

 

pump

 

must

 

be

 

installed

 

with

 

no

 

duct

 

work

 

in

 

the

 

airstream.

 

The

 

outdoor

 

fan

 

is

 

not

 

designed

 

to

 

operate

 

against

 

any

 

additional

 

static

 

pressure.

 

 

1.1. TOOLS AND PARTS

 

Assemble

 

the

 

required

 

tools

 

before

 

starting

 

installation.

 

Read

 

and

 

follow

 

the

 

instructions

 

provided

 

with

 

any

 

tools

 

listed

 

here.

 

        

Tools

 

Needed:

 



Mechanical

 

tools

 

required

 

by

 

Plumbing

 

or

 

HVAC

 

standards

 



Wrenches,

 

Screw

 

Drivers,

 

Hose,

 

Glycol

 

        

Parts

 

Needed:

 

Check

 

local

 

codes

 

and

 

HVAC

 

supplier.

 

Check

 

existing

 

electrical

 

supply,

 

and

 

read

 

“Electrical

 

Requirements,”

 

“Location

 

Requirements,”

 

“System

 

Requirements”

 

and

 

“Connect

 

Glycol

 

Lines.”

 

 

1.2 SYSTEM REQUIREMENTS:

 

Aermec

 

heat

 

pump

 

system

 

are

 

derived

 

from

 

actual

 

laboratory

 

testing

 

of

 

the

 

equipment.

 

It

 

is

 

recommended

 

that

 

all

 

deisgn

 

criteria

 

be

 

met

 

or

 

exceeded

 

to

 

ensure

 

proper

 

operation

 

and

 

efficient

 

performance.

 



The

 

designed

 

system

 

criteria

 

are

 

listed

 

in

 

the

 

heat

 

pump

 

unit

 

specification

 

sheets

 

and

 

in

 

the

 

heat

 

pump

 

technical

 

man

ual

 



  

This

 

heat

 

pump

 

has

 

been

 

factory

 

charged

 

with

 

a

 

quantity

 

of

 

refrigerant

 

(R410A)

  

 

1.3 LOCATION REQUIREMENTS 

 



 

This

 

heat

 

pump

 

is

 

designed

 

to

 

be

 

located

 

outdoors

 

with

 

sufficient

 

clearance

 

for

 

free

 

entrance

 

to

 

the

 

inlet

 

and

 

discharge

 

air

 

openings.

 

The

 

location

 

must

 

also

 

allow

 

for

 

adequate

 

service

 

access.

 

See

 

“Minimum

 

Clearances.”

 



Where

 

possible,

 

select

 

a

 

location

 

for

 

the

 

heat

 

pump

 

which

 

is

 

shaded

 

from

 

the

 

direct

 

rays

 

of

 

the

 

sun

 

most

 

of

 

the

 

time.

 

North

 

or

 

east

 

locations

 

are

 

usually

 

most

 

desirable.

 

Position

 

the

 

heat

 

pump

 

to

 

avoid

 

direct

 

contact

 

with

 

water,

 

snow

 

or

 

ice

 

from

 

a

 

roof

 

line

 

overhead.

 



The

 

heat

 

pump

 

must

 

be

 

installed

 

on

 

a

 

solid,

 

level

 

mounting

 

pad

 

that

 

will

 

not

 

settle

 

or

 

shift.

 

Isolate

 

the

 

pad

 

from

 

the

 

building

 

structure

 

to

 

avoid

 

possible

 

transmission

 

of

 

sound

 

or

 

vibration

 

from

 

the

 

heat

 

pump

 

into

 

the

 

conditioned

 

space.

 



The

 

heat

 

pump

 

foundation

 

should

 

be

 

raised

 

to

 

a

 

minimum

 

of

 

3

 

in.

 

above

 

finish

 

grade.

 

In

 

areas

 

which

 

have

 

prolonged

 

periods

 

of

 

temperatures

 

below

 

freezing,

 

and/or

 

snowfall,

 

the

 

heat

 

pump

 

should

 

be

 

elevated

 

above

 

the

 

average

 

snow

 

line.

 

If

 

heat

 

pump

 

is

 

to

 

be

 

installed

 

on

 

a

 

flat

 

roof,

 

it

 

should

 

be

 

on

 

a

 

platform

 

or

 

other

 

support

 

which

 

will

 

raise

 

the

 

unit

 

base

 

pan

 

12

 

in.

 

minimum

 

above

 

the

 

surface

 

of

 

the

 

flat

 

roof.

 



Care

 

should

 

be

 

taken

 

to

 

ensure

 

free

 

drainage

 

of

 

condensate

 

from

 

defrost

 

cycles.

 

This

 

will

 

prevent

 

ice

 

accumulation.

 

The

 

heat

 

pump

 

should

 

be

 

located

 

away

 

from

 

walkways

 

to

 

prevent

 

possible

 

icing

 

from

 

defrost

 

condensate.

 



Avoid

 

placing

 

the

 

heat

 

pump

 

near

 

areas

 

such

 

as

 

sleeping

 

quarters

 

or

 

study

 

rooms.

 

Normal

 

operating

 

sound

 

levels

 

may

 

be

 

objectionable

 

if

 

the

 

heat

 

pump

 

is

 

placed

 

near

 

certain

 

rooms.

 

A

 

shift

 

in

 

sound

 

type

 

does

 

occur

 

during

 

the

 

defrost

 

mode.

 

The

 

defrost

 

mode

 

generally

 

lasts

 

no

 

longer

 

than

 

5

 

minutes

 

1. INSTALLATION REQUIRMENTS 

1.5 MINIMUM CLEARENCE

 

1.4 MINIMUM WATER VOLUME

 

IMPORTANT:

 

Refer

 

to

 

“Aermec

 

System

 

Water

 

Volume

 

Guide”

 

(you

 

can

 

download

 

it

 

on

 

aermec.us

 

in

 

tutorial

 

books

 

section)

 



ANK

 

heat

 

pumps

 

need

 

a

 

minimum

 

volume

 

of

 

35

 

gallons

 

of

 

water/glycol.

 

If

 

the

 

version

 

is

 

an

 

HA

 

it

 

has

 

an

 

internal

 

25

 

gallon

 

tank

 

so

 

the

 

system

 

must

 

contain

 

a

 

minimum

 

of

 

10

 

additional

 

gallons

 

when

 

all

  

zones

 

but

 

the

 

smallest

 

are

 

closed

 

or

 

not

 

operating.

 

(Only

 

count

 

the

 

smallest

 

zone

 

volume

 

along

 

with

 

the

 

pipes

 

to

 

the

 

manifold.

 

 



If

 

the

 

heat

 

pump

 

does

 

not

 

have

 

an

 

internal

 

buffer

 

tank

 

you

 

must

 

add

 

35

 

gallons

 

in

 

the

 

system

 

with

 

a

 

buffer

 

tank

 

or

 

piping.

  

Содержание ANK

Страница 1: ... 7 5 7 WATER FLOW RATE ALARM 8 6 MAINTENANCE 8 6 1 HYDRAULIC CIRCUIT 8 6 2 ELECTRICAL CIRCUIT CHECKS 8 6 3 COOLING CIRCUIT CHECKS 8 6 4 MECHANICAL CHECKS 8 6 5 REFRIGERANT LOAD PROCEDURE 8 7 LIST OF CONTROLS 9 8 TROUBLESHOOTING 11 WIRING DIAGRAM 12 WARRANTY 13 ANK INSTALLATION MANUAL NORTH AMERICAN REVISION Table of contents GENERAL WARNING FOR THE INSTALLER The chiller must be installed by a qual...

Страница 2: ...ly most desirable Position the heat pump to avoid direct contact with water snow or ice from a roof line overhead The heat pump must be installed on a solid level mounting pad that will not settle or shift Isolate the pad from the building structure to avoid possible transmission of sound or vibration from the heat pump into the conditioned space The heat pump foundation should be raised to a mini...

Страница 3: ...gs connected from the disconnect to the heat pump shall be rated for outdoor use Check the heat pump rating plate and follow the appropriate instructions below NOTE All wiring must be suitable for outdoor use Use copper conductors only All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable Electrical wiri...

Страница 4: ...sized minimum 1 inch Reducing fitting shall not be used Use care with the water glycol lines during the installation process If pex is used it can be cut by sharp objects Do not remove the caps from the lines or system connection points until connections are ready to be completed 1 Route the supply and return lines from the fittings on the indoor manifold or tank to the fittings on the heat pump R...

Страница 5: ...it Position the main system switch external to the appliance at ON 2 2ELECTRICAL CONNECTIONS The ANK heat pumps are completely wired at the factoryand only require connection to the electrical mains downstream from a unit switch according to that envisioned by the Standards in force on this subject in the country of installation It s also advised to check the following The electrical mains feature...

Страница 6: ...LED see subsequent pages 4 CONTROLS AND COMMISSIONING 4 1 PREPARATION FOR COMMISSIONING Before starting the unit make sure that 1 All safety conditions have been respected 2 The unit is correctly fixed to the support surface 3 The minimum technical spaces have been respected 4 The hydraulic connections have been made respecting theinlet and outlet 5 The hydraulic plant has been loaded and bled of ...

Страница 7: ...he temperature detected by the probe postioned at the outlet of the heat exchanger and in inlet to the chiller is below 4 C 39 F THIS ANTI FREEZE SET TEMPERATURE CAN ONLY BE VARIED BY AN AUTHORISED AFTER SALES CENTRE AND ONLY AFTER HAVING CHECKED THAT THERE IS ANTI FREEZE SOLUTION IN THE WATER SYSTEM The intervention of this alarm determines compressor stop and not pump block which remains active ...

Страница 8: ...WHENEVER THIS ALARM INTERVENES WE ADVISE YOU CALL THE NEAR EST AFTER SALES SERVICE IMMEDIATELY 5 7 WATER FLOW RATE ALARM The MODUCONTROL manages a water flow rate alarm controlled by the differential pressure switch installed in series on the machine This type of safety device intervenes after the first 40 seconds of pump function ing if the water flow rate is not sufficient The intervention of th...

Страница 9: ...in Fig B To confirm the modification press the key shown in Fig A again 7 LIST OF CONTROLS FOR THE GUIDED PROCEDURE How to modify a parameter in the user menu To enter the USER menu press the key shown in Fig A Once the key has been pressed the password must be inserted for access to the various menus To access the user menu the password is 000 which is the de fault displayed to modify the value o...

Страница 10: ...on 5 Envisioned Set the parameter ASA index A INSTALLER MENU with the value 1 4 Is a 3 way diverter valve envisioned in the DHW production circuit Reply Operations to be performed Not envisioned Go to question 5 Envisioned Set the parameter AAS index C INSTALLER menu with the appropriate value in seconds This parameter indicates the stand by tome for inversion of the 3 way diverter valve on the DH...

Страница 11: ...rational limits Check Pressure switch dysfunction Replace the component Circuit breaker protection interruption Check power supply voltage Check electric isolation of the windings High discharge pressure High external air temperature High water input temperature Check Insufficient air flow Insufficient water flow Check fan functioning Check pump functioning Fan regulation anomalous functioning Che...

Страница 12: ...iler control C F IA AE REF CEI EN 60335 2 40 ATTENTION all others give a reinforced insulation opposed to main power supply line Terminals 6 and 7 provide basic insulation 2RCR 1RCR RCR2 M7S 5 M7S 7 M7S 8 M1 8 M1S 8 M5S1 1 M5S1 2 M7 6 M7 5 M7S 4 M7S 3 RCR1 Contact between 4 5 opened unit off closed unit on Contact between 3 5 opened unit oin heating closed unit on Contact between 10 11 opened unit...

Страница 13: ...roper materials or workmanship as determined by MITS the company will at its sole discretion replace the defective part or component Conditions In the event MITS replaces a part or component the repaired or replaced product shall be warranted under the original limited warranty for the remainder of the original warranty period The warranty does not cover any failure of components not supplied by M...

Страница 14: ...nding Aermec reserves the right to apply at any time all the modifications deemed necessary for improving the product 1608 Bonhill Road Mississauga ON CA L5T 1C7 Phone 905 564 2221 Canada www aermec ca Toll Free 1 800 567 2221 US www aermec us Toll Free 1 888 567 2227 ...

Отзывы: