background image

aerl 

COMMS MANUAL 

 

COOLMAX SR 

Australian Energy Research Laboratories, Pty.Ltd 

AER07.004 – Version G2 v9 

13

th

 January 2016 

 

 

 

7 of 21 

3.4

 

SHIELDING 

 

Correct shielding practice is important for error free communications. Incorrect shielding can cause 
more  interference  than  unshielded  cables  would  experience.  Shields  should  be  linked  between 
each  wire  segment  along  the  network  but  only  grounded  in  one  place.  The  following  paragraphs 
explain how to achieve this. 

The shield should be wired through the entire network independently of the ground and connected 
to  ground  at  the  end  of  the  network  and  nowhere  else  in  the  network. This  is  shown  at  the  right 
hand end of the example network in 

Figure 2.

 

3.5

 

MODBUS TERMINATION 

A 120 Ω resistor needs to be wired between the Modbus-A and Modbus-B lines at either end of the 
linear  network  in  order  to  terminate  both  ends  of  the  network. At  the  far  end  of  the  network  the 
resistor can be simply installed into the last terminal block. 

If  no  Modbus-Ethernet  Bridge  adapter  is  present  on  the  network  the  same  terminal  block  style 
termination can  be made on the other end  of the  network. However,  if a Modbus-Ethernet Bridge 
adapter is present on the network, it can be used to terminate the network by wiring a  termination 
resistor across Modbus-A and Modbus-B on the unused header. 

 

3.6

 

MODBUS MEMORY MAP (DISCRETE INPUTS) 

Single−Bit (Read−Only) 
Returns : 

0 to 255 (

byte

 data type) 0x00 to 0xFF (i.e. 8 Bits) 

Notes :  

When  a  request  is  sent  to  read  a  discrete  input,  a  byte  is  returned  containing  the  values  of  8 
consecutive inputs, with the addressed input as the LSB. If the returned input quantity is not a multiple 
of 8 bits, then the final data byte is padded with zeros. 

 

Memory 

Offset 

Input Address 

Description 

Input 

Range 

Data 

Range 

Read/Write 

Comment 

− 

10000 

− 

− 

− 

− 

− 

10001 

ACTIVE EVENTS 

System Power 

Bit 

0 or 1 

Read−Write 

 Event 

Cleared 

 Event 

Triggered 

10002 

ACTIVE EVENTS 

Low Out Voltage 
Warning 

Bit 

0 or 1 

Read−Write 

 Event 

Cleared 

 Event 

Triggered 

10003 

ACTIVE EVENTS 

Low Out Voltage Fault 

Bit 

0 or 1 

Read−Write 

 Event 

Cleared 

 Event 

Triggered 

10004 

ACTIVE EVENTS 

Low Out Voltage 
Gen−Set 

Bit 

0 or 1 

Read−Write 

 Event 

Cleared 

 Event 

Triggered 

10005 

ACTIVE EVENTS 

High Out Voltage Fault 

Bit 

0 or 1 

Read−Write 

 Event 

Cleared 

 Event 

Triggered 

Important 

Содержание COOLMAX SR

Страница 1: ...aerl COMMS MANUAL COOLMAX SR Australian Energy Research Laboratories Pty Ltd AER07 004 Version G2 v9 13 th January 2016 COOLMAX SR MAXIMIZER WALLMOUNT Communications User Manual Models SRMVW SRHVW...

Страница 2: ...dbus Wiring 6 3 4 Shielding 7 3 5 Modbus Termination 7 3 6 Modbus Memory Map Discrete Inputs 7 4 Can Communications 16 4 1 CAN Network Topology 16 4 2 CAN Wiring 17 4 3 Shielding 18 4 4 CAN Terminatio...

Страница 3: ...ead before begin ning installation Only qualified electricians and technicians should install the COOLMAX SR System This manual is intended for all Installation technicians and the system owner Do not...

Страница 4: ...ng but not limited to condensation moisture damage and other forms of precipitation 6 The Product is not covered for damage occurring due to the Product being incorrectly installed or installed in a m...

Страница 5: ...Removal of the Access Panel Important All COOLMAX SR wiring must enter the unit via a 40mm conduit fitting at the bottom of the unit Drilling holes into the unit to make any other cable entry point w...

Страница 6: ...OPOLOGY Multiple COOLMAX SR units can exist on the same Modbus and this can be connected to other networks using a Modbus Ethernet Bridge adaptor The Modbus is structured as a linear network with shor...

Страница 7: ...e ideally with another twisted pair to minimise noise pickup An overall shield can also be advantageous Standard CAT5 network cabling which has an impedance of 100 can be used but may become unreliabl...

Страница 8: ...rminal block style termination can be made on the other end of the network However if a Modbus Ethernet Bridge adapter is present on the network it can be used to terminate the network by wiring a ter...

Страница 9: ...ature Sensor Fault Bit 0 or 1 Read Write 0 Event Cleared 1 Event Triggered 11 10012 ACTIVE EVENTS Negative PV Current Shutdown Bit 0 or 1 Read Write 0 Event Cleared 1 Event Triggered Memory Offset Inp...

Страница 10: ...ACTIVE EVENTS Not Used Bit 0 or 1 Read Write Reserved 26 10027 ACTIVE EVENTS Not Used Bit 0 or 1 Read Write Reserved 27 10028 ACTIVE EVENTS Not Used Bit 0 or 1 Read Write Reserved Memory Offset Input...

Страница 11: ...cs Not Used Bit 0 or 1 Read Only Reserved 43 10044 STATUS Statistics Not Used Bit 0 or 1 Read Only Reserved 44 10045 STATUS Statistics Not Used Bit 0 or 1 Read Only Reserved Memory Offset Input Addres...

Страница 12: ...0 or 1 Read Only Reserved 65 10066 STATUS Communications Not Used Bit 0 or 1 Read Only Reserved 66 10067 STATUS Communications Not Used Bit 0 or 1 Read Only Reserved 67 10068 STATUS Communications Not...

Страница 13: ...ontrol Mode Bit 0 or 1 Read Only 0 MPPT 1 Output Voltage 2 Input Voltage 3 Not Used 83 10084 84 10085 STATUS Control Not Used Bit 0 or 1 Read Only Reserved Memory Offset Input Address Description Inpu...

Страница 14: ...t ID Byte 5 High Product ID Byte 6 Low 3 30004 16 Bits 0 to 65535 Read Only Product ID Byte 7 High Product ID Byte 8 Low 4 30005 LIVE TELEMETRY Serial Number 8 Characters 16 Bits 0 to 65535 Read Only...

Страница 15: ...High Out Current Byte 4 Low 24 30025 LIVE TELEMETRY Active Events Uint32 16 Bits 0 to 65535 Read Only Active Events Byte 1 High Active Events Byte 2 Low 25 30026 16 Bits 0 to 65535 Read Only Active Ev...

Страница 16: ...Low 50 30051 SYSTEM INFO Product ID 8 Characters 16 Bits 0 to 65535 Read Only Product ID Byte 1 High Product ID Byte 2 Low 51 30052 16 Bits 0 to 65535 Read Only Product ID Byte 3 High Product ID Byte...

Страница 17: ...ed as a linear network with short stubs branching from T connectors on the main bus backbone to each device The CAN bus data lines must be terminated at each end of the main bus with 120 resistors bet...

Страница 18: ...AWG data 22 AWG power twisted pairs and a braided shield Using this cable will result in a robust installation Standard CAT5 network cabling which has an impedance of 100 can be used but may become u...

Страница 19: ...CAN GND J3 3 SHIELD YES J3 4 CAN H Digital IO CAN signals J3 5 CAN L J3 6 NC Table 1 Signal PIN Assignment 4 3 SHIELDING Correct shielding practice is important for error free communications Incorrect...

Страница 20: ...EE single precision 32 bit format IEEE 754 with most significant byte MSB sent first Bit Length 1 11 6 8 Bytes 16 2 7 Start Identifier Control Data Field CRC Ack End Figure 2 CAN Data Frame 3 7 3 Iden...

Страница 21: ...surement ID COOLMAX SR Base Address 1 Variable Bits Type Description PV Current 63 32 float PV Current PV Voltage 31 0 float PV Voltage 3 8 3 Output Voltage Current Measurement ID COOLMAX SR Base Addr...

Страница 22: ...Boolean High battery temp fault Bat current 5 Boolean High battery discharge current fault Iout fault 4 Boolean High output current fault Vout high fault 3 Boolean High output voltage fault Not used 2...

Отзывы: