Please consider: 

Humidity values of a minimum of 40 % - 45 % r.h. can be achieved with a 
condensation dryer. In a swimming pool room a humidity of approx. 60% r.h. is 
recommended. 

 

6.8 Automatic defrost 

 

During air drying, ice may form at the evaporator. The volume of ice depends on the 
ambient conditions prevailing in the room to be dried. The air dryer is equipped with 
an automatic air-defroster. It ensures that, depending on the extent of ice formation, 
the appliance will be defrosted automatically according to the following principle: 

Ø

  A temperature sensor measures the condition existing in a critical area of the 

evaporator. 

Ø

  It transmits the signal for defrosting to the DryLogic-electronic. The DryLogic 

finds out if defrosting is necessary, and it will start defrost-mode on its own. 

Ø

  During defrosting the fan works and the compressor does not work. That means 

the ice is defrosted by the ambient air. 

Ø

  When the ice is defrosted, the dehumidifier will start again with dehumidifying. 

 

6.9 Thermal protection 
 

The AP-series are equipped with the thermal protection „ThermoLogic”. The 
“ThermoLogic” switches the compressor off if the ambient temperature is higher / 
lower than the allowed working range. (> +32°C / < +3°C). As soon as the allowed 
temperature has reached, the compressor switches on again automatically. 
If the Thermologic switched the compressor off, this is indicated to the red signal 
light by permanent lighting up. 

 
7. Service and maintenance 

 

ATTENTION 

When performing any repair or maintenance, the general safety rules and 
provisions must be adhered to! 

 

 
In order to guarantee a troublefree function of the dryer the device should be 
cleaned regularly. The following procedure is instead recommended: 

Ø

  Check function of connected hygrostat. 

Ø

  Switch the unit off at the main power switch 

Ø

  Remove the cover. No tool is necessary, pull off simply. The cover must be put 

down cautiously on a tender subsoil that they do not topple over and it can not 
come to disadvantages at the surface. 

Ø

  Clean the heat exchangers (evaporator and condenser) for example with a 

brush or with air. Remove the dust from the lamellae. 

Attention: The lamellae 

are sharp-edged. Risk of injury! 

Ø

  Check the drain and the hose. Make sure that the condensate can flow off 

certainly. 

Ø

  Mount the cover. 

Ø

  Clean the case with a moist towel. Do not use aggressive Detergent. 

Ø

  Switch on the main power switch. 

This cleaning is required 4 x  a year! 

No other maintenance work is required for the air dryer. 

Содержание AP 50

Страница 1: ...page 1 of 17 Instruction manual _____________________________________ Swimming pool dehumidifier AP 50 AP 70 _____________________________________ Valid 12 2010...

Страница 2: ...P 70 8 6 Installation and transport 9 6 1 Place of installation 9 6 2 Fixing at a wall 9 6 3 Electrical connection 10 6 4 Condensate removal 10 6 5 Add fresh air 11 6 6 Putting into operation 11 6 7 H...

Страница 3: ...ping in order to be able to send the device safe for guarantee repair In order to save space you open simply the adhesive tape with a knife and you fold the carton 2 Mode of functioning The AP air dry...

Страница 4: ...ected The condensation dryers are intended for the drying of air with atmospheric pressure Risk by accessory Hoses for condensate removal must be fit expertly and must not take the protective devices...

Страница 5: ...atmospheres for example ammonia and wood acid high chlorine concentration In rooms with water which shows a pH value outside of 7 0 to 7 4 Remark In The case of lower pH value corrosion occurs at all...

Страница 6: ...2 3 Connection box for electrical supply see 6 3 4 Cable entries see 6 3 5 Room temperature sensor for ThermoLogic see 6 9 6 Spacer distance to the wall 7 Bleed air fresh air aperture see 6 5 8 Apertu...

Страница 7: ...d 4 Cover for e box 5 Cover for compressor 5 3 Operation panel On Off switch Neon green Voltage on Neon green defrost mode Hygrostat see hygrostat control 6 7 Unit has been switched off because adjust...

Страница 8: ...page 8 of 17 5 4 Dimensions AP 50 5 5 Dimensions AP 70...

Страница 9: ...pirit level on all axles accurately ATTENTION The dryer is not suitable as seat furniture Damages by inappropriate treatment and use lead to expiring the guarantee 6 1 Place of Installation ATTENTION...

Страница 10: ...cm per meter away from the dryer into a discharge The condensate connector is factory installed left down at the machine Depending on the situation in the room the connector can also be changed to th...

Страница 11: ...Hygrostat control The air dryers of the AP series dispose of a hygrostat for setting the required humidity value This hygrostat is located in the operation panel It makes that the air dryer cuts in as...

Страница 12: ...if the ambient temperature is higher lower than the allowed working range 32 C 3 C As soon as the allowed temperature has reached the compressor switches on again automatically If the Thermologic swi...

Страница 13: ...sions width height depth 824 mm 740 mm 261 mm weight 54 kg refrigerant CFC free R134a filling charge see type plate Capacity in acc to DIN EN 810 E Temperature relative humidity capacity l day Power c...

Страница 14: ...does not run Is the unit supplied with voltage Check the main cable and the main fuse The humidity value adjusted at the hygrostat is achieved The dryer will start again after exceeding the adjusted...

Страница 15: ...ons of AERIAL air dryers we recommend get in touch with your supplier The producer AERIAL GmbH you reach under 0049 40 526879 0 or www aerial de 10 Disposal Please do not dispose this unit with the do...

Страница 16: ...page 16 of 17 11 circuit diagram AP 50 AP 70...

Страница 17: ...yer ready for connection Related standards EN ISO 12100 Safety of Machinery EN 61 000 Electromagnetic Compatibility EMC Basic Specification Emitted Interference EN 60 335 2 40 Safety of electric appli...

Отзывы: