Please consider:
Humidity values of a minimum of 40 % - 45 % r.h. can be achieved with a
condensation dryer. In a swimming pool room a humidity of approx. 60% r.h. is
recommended.
6.8 Automatic defrost
During air drying, ice may form at the evaporator. The volume of ice depends on the
ambient conditions prevailing in the room to be dried. The air dryer is equipped with
an automatic air-defroster. It ensures that, depending on the extent of ice formation,
the appliance will be defrosted automatically according to the following principle:
Ø
A temperature sensor measures the condition existing in a critical area of the
evaporator.
Ø
It transmits the signal for defrosting to the DryLogic-electronic. The DryLogic
finds out if defrosting is necessary, and it will start defrost-mode on its own.
Ø
During defrosting the fan works and the compressor does not work. That means
the ice is defrosted by the ambient air.
Ø
When the ice is defrosted, the dehumidifier will start again with dehumidifying.
6.9 Thermal protection
The AP-series are equipped with the thermal protection „ThermoLogic”. The
“ThermoLogic” switches the compressor off if the ambient temperature is higher /
lower than the allowed working range. (> +32°C / < +3°C). As soon as the allowed
temperature has reached, the compressor switches on again automatically.
If the Thermologic switched the compressor off, this is indicated to the red signal
light by permanent lighting up.
7. Service and maintenance
ATTENTION
When performing any repair or maintenance, the general safety rules and
provisions must be adhered to!
In order to guarantee a troublefree function of the dryer the device should be
cleaned regularly. The following procedure is instead recommended:
Ø
Check function of connected hygrostat.
Ø
Switch the unit off at the main power switch
Ø
Remove the cover. No tool is necessary, pull off simply. The cover must be put
down cautiously on a tender subsoil that they do not topple over and it can not
come to disadvantages at the surface.
Ø
Clean the heat exchangers (evaporator and condenser) for example with a
brush or with air. Remove the dust from the lamellae.
Attention: The lamellae
are sharp-edged. Risk of injury!
Ø
Check the drain and the hose. Make sure that the condensate can flow off
certainly.
Ø
Mount the cover.
Ø
Clean the case with a moist towel. Do not use aggressive Detergent.
Ø
Switch on the main power switch.
This cleaning is required 4 x a year!
No other maintenance work is required for the air dryer.