9.Trouble shooting 

 

Assign that dehumidifier a putative defect on, please, first check the following points. 
If this should provide no relief, please contact your technical consultant. 
 
1) 

The dehumidifier shows a bad or no drying capacity

 

- The humidity is lower than 40% r.h. or the temperature in that room is lower than  
   +10°C. The using of the dryer is uneconomical in the case of these conditions. It  
   is recommended to disconnect the dryer. 

Tipp

: Put the built-in hygrostat on an  

   attainable value (e.g. approx. 60%r.F. in swimming pool rooms), with it the dryer  
   punctually may switch off. 
-  The heat exchangers are soiled. Not enough air flows through the dryer.

 Tipp

Lead regularly maintenance as described in point 8! 

 
2) 

The compressor of the dehumidifier does not work

-  The unit is in defrost mode. In this case the fan still runs and the compressor does 

not run. After some minutes, the unit will start with regular working.(see 6.8) 

-  The ambient temperature in that room is lower than +3°C or higher than +32°C. 

The unit will start again when the temperature in that room has achieved normal 
conditions between  +3°C and +32°C (see 6.9). 

 
3) 

The complete dryer is out of operation. Fan and compressor does not run

-  Is the unit supplied with voltage? Check the main cable and the main fuse.  
-  The humidity value adjusted at the hygrostat is achieved. The dryer will start again 

after exceeding the adjusted humidity.(see 6.7) 

 
4) 

The humidity adjusted at the hygrostat does not become achieved and/or the 

device does not switch off automatic

-  Is the hygrostat adjusted on a value lower than 40 – 45% r.h.? Humidity values  

with a minimum of 40 % - 45 % r.h. can be achieved with a condensation dryer. 
Adjust the hygrostat to a reachable value. (in swimming halls for exa,ple 60% r.h.) 

-  Is the unit with enough capacity for your application? The ambient temperature, 

the water temperature, water movement and the open water surfaces decide 
among other things on the dampness load in the area. Let calculate the necessary 
capacity from your dealer. 

-  Is there a lot of water in the walls or the floor? In that case the dryer needs some 

time to remove that water and to achieve an acceptable humidity in that room 

 
5) 

Water runs beside the dryer

- Make sure that the dryer stands accurately straight on all axles (spirit level!) 
- Make sure that the drain hose is surely fastened to hose connector. 
- Make sure the drain hose is shifted away from the unit with enough slope. 
- Examine whether the drain hose is free from the inside. In the course of the time it  
  can be blocked by algae.  
- Make sure that the hose end is not in the water 

 
 
 
 
 
 
 

Содержание AP 50

Страница 1: ...page 1 of 17 Instruction manual _____________________________________ Swimming pool dehumidifier AP 50 AP 70 _____________________________________ Valid 12 2010...

Страница 2: ...P 70 8 6 Installation and transport 9 6 1 Place of installation 9 6 2 Fixing at a wall 9 6 3 Electrical connection 10 6 4 Condensate removal 10 6 5 Add fresh air 11 6 6 Putting into operation 11 6 7 H...

Страница 3: ...ping in order to be able to send the device safe for guarantee repair In order to save space you open simply the adhesive tape with a knife and you fold the carton 2 Mode of functioning The AP air dry...

Страница 4: ...ected The condensation dryers are intended for the drying of air with atmospheric pressure Risk by accessory Hoses for condensate removal must be fit expertly and must not take the protective devices...

Страница 5: ...atmospheres for example ammonia and wood acid high chlorine concentration In rooms with water which shows a pH value outside of 7 0 to 7 4 Remark In The case of lower pH value corrosion occurs at all...

Страница 6: ...2 3 Connection box for electrical supply see 6 3 4 Cable entries see 6 3 5 Room temperature sensor for ThermoLogic see 6 9 6 Spacer distance to the wall 7 Bleed air fresh air aperture see 6 5 8 Apertu...

Страница 7: ...d 4 Cover for e box 5 Cover for compressor 5 3 Operation panel On Off switch Neon green Voltage on Neon green defrost mode Hygrostat see hygrostat control 6 7 Unit has been switched off because adjust...

Страница 8: ...page 8 of 17 5 4 Dimensions AP 50 5 5 Dimensions AP 70...

Страница 9: ...pirit level on all axles accurately ATTENTION The dryer is not suitable as seat furniture Damages by inappropriate treatment and use lead to expiring the guarantee 6 1 Place of Installation ATTENTION...

Страница 10: ...cm per meter away from the dryer into a discharge The condensate connector is factory installed left down at the machine Depending on the situation in the room the connector can also be changed to th...

Страница 11: ...Hygrostat control The air dryers of the AP series dispose of a hygrostat for setting the required humidity value This hygrostat is located in the operation panel It makes that the air dryer cuts in as...

Страница 12: ...if the ambient temperature is higher lower than the allowed working range 32 C 3 C As soon as the allowed temperature has reached the compressor switches on again automatically If the Thermologic swi...

Страница 13: ...sions width height depth 824 mm 740 mm 261 mm weight 54 kg refrigerant CFC free R134a filling charge see type plate Capacity in acc to DIN EN 810 E Temperature relative humidity capacity l day Power c...

Страница 14: ...does not run Is the unit supplied with voltage Check the main cable and the main fuse The humidity value adjusted at the hygrostat is achieved The dryer will start again after exceeding the adjusted...

Страница 15: ...ons of AERIAL air dryers we recommend get in touch with your supplier The producer AERIAL GmbH you reach under 0049 40 526879 0 or www aerial de 10 Disposal Please do not dispose this unit with the do...

Страница 16: ...page 16 of 17 11 circuit diagram AP 50 AP 70...

Страница 17: ...yer ready for connection Related standards EN ISO 12100 Safety of Machinery EN 61 000 Electromagnetic Compatibility EMC Basic Specification Emitted Interference EN 60 335 2 40 Safety of electric appli...

Отзывы: