Maximum Gas Pressure Switch Adjustment
11.8.2
Adjust the maximum gas pressure switch in Figure 11-14 after having performed all other burner
adjustments with the maximum gas pressure switch set to the end of the scale.
Adjusting Maximum Gas Pressure Switch
1. With the burner operating at MAX output, reduce the adjustment pressure by slowly turning
the adjustment dial anticlockwise until the burner locks out.
2. Then turn the dial clockwise by 0.8” WC and repeat burner firing.
3. If the burner locks out again, turn the dial again clockwise by 0.4” W.C.
Figure 11-14: Maximum Gas Pressure Switch
Minimum Gas Pressure Switch Adjustment
11.8.3
Adjust the minimum gas pressure switch in Figure 11-15 after having performed all the other
burner adjustments with the pressure switch set at the start of the scale.
Adjusting the Minimum Gas Pressure Switch
1. With the burner operating at MAX output, increase adjustment pressure by slowly turning
the relative dial clockwise until the burner locks out.
2. Then turn the dial anti-clockwise by 0.8” WC and repeat burner starting to ensure it is
uniform.
3. If the burner locks out again, turn the dial anti-clockwise again by 0.4” W.C.
Figure 11-15: Minimum Gas Pressure Switch