MFC Series Boilers User Manual
CHAPTER 8 – MFC 4000/6000 DUAL FUEL BURNER
P
OMM-0104_94
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
79
of
170
GF-146
Ph.: 800-526-0288
12/29/2015
8.10 Hydraulic Connections
The pumps are equipped with a by-pass that separates return line and suction line in Figure 8-
14. The pumps are installed on the burner with the by-pass closed by screw (6). It is therefore
necessary to connect both hoses to the pump.
CAUTION!
DO NOT run the pump with the return line closed and the by-pass screw inserted, or the pump
will be quickly damaged. Remove the plugs from the suction and return connections of the
pump.
Connecting the Hydraulics
1. Remove the plugs from the suction and return connections of the pump.
2. Insert the hose connections with the supplied seals into the connections and screw them
down.
CAUTION!
Take care that the hoses are not stretched or twisted during installation.
3. Install the hoses where they cannot be stepped on or come into contact with hot surfaces
of the boiler.
4. Now connect the other end of the hoses to the suction and return lines.
Figure 8-14: Connecting the Hydraulics
A