INSTALLATION
2-4
To avoid damage to the unit, when pressure
testing gas piping, isolate the unit from the gas
supply piping. At no time should there be more
than 14” W.C. to the unit. Leak test all external
piping thoroughly for leaks using a soap and
water solution or suitable equivalent. The gas
piping must meet all applicable codes.
2.4.1 GAS SUPPLY SPECIFICATONS
AND GAS SUPPLY REGULATORS
The maximum static pressure to the unit must
be no more than 14” W.C. Minimum operating
gas pressure is 7” W.C. when the unit is firing at
maximum input. Proper sizing of the gas supply
regulator in delivering the correct gas flow and
outlet pressure is mandatory. The gas supply
pressure regulator must be of sufficient capacity
volume to provide 2000 cfh while maintaining
the gas pressure at 7” W.C., for natural gas, and
should have no more than 1" droop from
minimum to full fire.
A Maxitrol RV-91 gas supply regulator is
supplied by AERCO and must be positioned as
shown in figure 2.7. Maximum gas pressure to
the RV-91 is 14" W.C. If the gas supply pressure
will exceed 14" W.C., a lock -up style regulator is
required up stream of the RV-91.
When installing the gas supply regulator(s),
union connections should be placed in the
proper locations to allow for maintenance.
The gas supply regulator must be properly
vented to outdoors. Consult the local gas utility
for exact
requirements concerning venting of
supply gas regulators.
NOTE:
If a regulator other than the Maxitrol RV-91
supplied with the boiler is used it must be
capable or regulating 2,000,000 BTU/HR of
natural gas while maintaining 7” W.C. to the
boiler.
CAUTION!
A lockup style regulator must be used when
gas supply pressure exceeds 14” W.C.
2.4.2 MANUAL GAS SHUTOFF VALVE
A 2” manual gas shut-off valve is furnished with
each unit. The valve should be positioned as
shown in Figure 2.7 upstream of the supply
regulator in a readily accessible location.
2.4.3 IRI GAS TRAIN KIT
The IRI gas train is an optional gas train
required in some areas by code or for insurance
purposes. The IRI gas train is factory pre-piped
and wired.
Figure 2.7
Gas Supply Regulator and Manual Shut-Off
Valve Location
2.5 ELECTRICAL SUPPLY
The AERCO Gas Fired Equipment Electrical
Power Wiring Guide, (GF-2060), must be
consulted in addition to the following material
before wiring to the unit is started. The location
of the A.C. electrical wiring connnections are
inside the control box as shown in Figure 2.8.
NOTE:
All electrical conduit and hardware should
be installed so that it does not interfere with
the removal of any cover, inhibit service or
maintenance, or prevent access between
the unit and walls or another unit.
GAS SUPPLY:
SEE GF-2030 FOR
COMPLETE GAS
PIPING INSTALLATION
DETAILS
Содержание Benchmark G-00-711
Страница 62: ...APPENDIX C ix Temperature Sensor Resistance Chart Balco ...
Страница 69: ...APPENDIX F xvi ...
Страница 70: ...APPENDIX F xvii ...
Страница 71: ...APPENDIX F xviii ...
Страница 72: ...APPENDIX F xix ...
Страница 73: ...APPENDIX F xx ...
Страница 74: ...APPENDIX G xviii ...
Страница 75: ...APPENDIX G xix ...
Страница 76: ...APPENDIX H xxi ...