BMK 5000-6000 Boiler OPERATION-SERVICE-MAINTENANCE GUIDE
SECTION 2: OPERATION
OMM-0124_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
27
of
136
GF-208
Ph.: 800-526-0288
05/02/2017
Table 2-8: Calibration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
12
Flue Material
PVC
Stainless
PVC
13
Exhst Fault Temp
100 °F
500 °F
200 °F
14
Exhst Module Temp
100 °F
500 °F
190 °F
15
Exhst Warn Temp
100 °F
500 °F
180 °F
16
Exhst Tmp VP Adj
0
10
5
17
Exhst Adj Rate
1
600
30
18
VP Change Rate
5
600
25
19
VP Up Rate
0.5
60.0
Depends on unit type/size
20
VP Down Rate
0.5
60.0
Depends on unit type/size
21
Purge Blwr Offst
-1.0
8.0
Depends on unit type/size
22
4-20mA Purge Pct
60%
100%
70%
23
PWM In Adj
-5.0%
5.0%
0.0%
24
Analog In Adj
-5.0%
5.0%
0.0%
25
Flow In Adj
-5.0%
5.0%
0.0%
26
Supply Gas Pressure In Adj
-5.0%
5.0%
0.0%
27
Gas Plate dp In Adj
-5.0%
5.0%
0.0%
28
mA Out Adj
-1.0 mA
1.0 mA
0.0 mA
29
A/F Sensitivity
1%
5%
2%
30
Power Reset
Automatic or Manual
Automatic
31
Water Temp Reset
Automatic or Manual
Automatic
32
Gas Press Reset
Automatic or Manual
Manual
33
Min Off Time
0 Min
15 Min
0 Min
34
Heatr Tuning Dsp
Enabled or Disabled
Disabled
35
Heatr Bkpt Dsp
Enabled or Disabled
Disabled
36
Stop Level
0%
Start Level
16
37
Start Level
Stop Level
40%
20
38
Skip Range Cntr
10
95
40
39
Skip Range Span
0
3
0
40
Skip Speed
0.5
2.0
0.5
41
O2 Gain
0.500
1.500
1.024
42
O2 Offset
-24.0
+2.0
0
43
O2 Sensor
Enabled or Disabled
Depends on unit type/size