BMK 5000-6000 Boiler OPERATION-SERVICE-MAINTENANCE GUIDE
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0124_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
87
of
136
GF-208
Ph.: 800-526-0288
05/02/2017
TABLE A-6: CALIBRATION MENU ITEM DESCRIPTIONS
See section 2-10 for a range of choices and the default values.
TABLE A-6: CALIBRATION MENU ITEM DESCRIPTIONS
MENU OPTION
DESCRIPTION
1
Stepper Fbk
Allows the Air/Fuel Valve stepper motor feedback current to be calibrated
at the 0% (fully closed) and 100% (fully open) positions. Verification can
also be accomplished at the 50% position.
2
Purge Timer
Allows adjustment of the pre-ignition purge time.
3
Post Purge Timer
Allows adjustment of the purge time when a unit shuts down.
4
IGN Position
Allows adjustment of the valve position (Fire Rate) during the ignition
sequence.
5
Ign Pos Hold Tmr
6
FFWD Temp Disply
7
FFWD Temp Disply
Enabled or Disabled.
8
Outlet Tmp Dsply
Enabled or Disabled.
9
Inlet Tmp Dsply
Enabled or Disabled.
10
Valv Pos Out Dsp
Enabled or Disabled.
11
Exhaust Tmp Dsp
Enabled or Disabled.
12
Exhaust Safety
13
Flue Material
14
Exhst Fault Temp
15
Exhst Module Temp
16
Exhst Warn Temp
17
Exhst Tmp VP Adj
18
Exhst Adj Rate
19
VP Change Rate
20
VP Up Rate
Allows adjustment of the Valve Position (Fire Rate) increase rate when
raising the Valve Position. VP Up Rate is defined as Seconds per Step.
21
VP Down Rate
Allows adjustment of the Valve Position (Fire Rate) decrease rate when
lowering the Valve Position. VP Down Rate is defined as Seconds per
Step.
22
Purge Blwr Offst
Allows adjustment of the blower speed (Blower Output Voltage) during the
Purge cycle.
23
4-20mA Purge Pct
Allows adjustment of the blower speed (Blower Output Voltage) during the
Purge cycle when using an Emerson VFD Drive to control the Blower
Motor.
24
PWM In Adj
Allows the Pulse Width Modulation (PWM) duty cycle to be adjusted from
-5.0% to +5.0% in 0.1% increments.
25
Analog In Adj
Allows adjustment of the analog input from -5.0% to +5.0%.