BMK 5000-6000 Boiler OPERATION-SERVICE-MAINTENANCE GUIDE
SECTION 5 – TROUBLESHOOTING GUIDE
OMM-0124_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
73
of
136
GF-208
Ph.: 800-526-0288
05/02/2017
TABLE 5-1: BOILER TROUBLESHOOTING PROCEDURES
FAULT
INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
STEPPER
MOTOR
FAILURE
1.
Air/Fuel Valve out of calibration.
2.
Air/Fuel Valve unplugged.
3.
Loose wiring connection to the stepper motor.
4.
Defective Air/Fuel Valve stepper motor.
5.
Defective Power Supply Board or fuse.
6.
Defective IGST Board.
1.
Refer to C-More User Manual, OMM-0032 (GF-112) and perform the
Stepper Feedback Calibration procedure in Section 6, section 6.2.1.
2.
Check that the Air/Fuel Valve is connected to the C-More Controller.
3.
.Inspect for loose connections between the Air/Fuel Valve motor and
the wiring harness.
4.
Replace stepper motor.
5.
Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
6.
Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every
second. If not, replace IGST Board.
SSOV FAULT
DURING
IGNITION
1.
SSOV didn’t open
1.
Check pilot assembly for carbon buildup.
2.
Check scanners sensed pilot flame.
3.
Check power through ignition relay.
4.
Scanners close neutral side of relay coil.