12
This option displays only if “Heating” is set on PRE or POST.
It allows to set the heating threshold in case of PRE or POST heating.
Press OK to enter.
Use
or
to set the temperature.
Press OK to select.
Setting ranges:
PRE: -20°C ÷ 0°C
POST: +15°C ÷ +25°C
The factory settings (DEFAULT) are:
PRE:-10°C
POST:+20°C
Installer menu
6 Heating
7 Heating Threshold
8 Dehumidification
9 Speed Setting
10 Airflow Balancing
To be selected only in case an external dehumidifier (not supplied) is present.
Press OK to enter.
Use
or
to choose NO or YES.
The factory setting (DEFAULT) is NO.
The DH relay output is activated when the HY input is activated (Fig.5.f) and the icon
is displayed.
Note: in case dehumidifier is installed, the BST input (Fig.5.f) is used as alarm output.
It allows to adjust the various speeds.
Press OK to enter.
Use
or
to choose speed 1, speed 2, speed 3 or Holiday.
Press OK to select.
The setting ranges are:
speed 1: 10% ÷ 80%
speed 2: 20% ÷ 90%
speed 3: 60% ÷ 100%
Holiday: 10% ÷ 40%
Use
or
to increase or decrease the speed percentage.
Press OK to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) are:
speed 1: 40%
speed 2: 70%
speed 3: 100%
Holiday: 20%
Installer menu
11 F7 filter
12 Filter Alarm interval
13 Working Hours Counter
14 Save settings
15 Load settings
To be selected only in case an F7 filter is installed at the supply air side (Fig.7.a)
Press OK to enter.
Use
or
to choose “Not installed” or “Installed”.
Press OK to select.
The factory setting (DEFAULT) is “Not Installed”.
Installer menu
6 Heating
7 Heating Threshold
8 Dehumidification
9 Speed Setting
10 Airflow Balancing
Installer menu
6 Heating
7 Heating Threshold
8 Dehumidification
9 Speed Setting
10 Airflow Balancing
Installer menu
6 Heating
7 Heating Threshold
8 Dehumidification
9 Speed Setting
10 Airflow Balancing
It allows to adjust the balancing of the two airflows.
Press OK to enter.
“Supply airflow” is highlighted.
Press OK to enter.
The setting range is: -20% ÷ +20%
Use
or
to adjust supply airflow against extract airflow
Press OK to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) is 0%
Содержание QR230E